2705.2.3.3 Drainage and Containment for HPM Liquids
JUMP TO FULL CODE CHAPTER
Each workstation utilizing HPM liquids shall have all of the following:
- Drainage piping systems connected to a compatible system for disposition of such liquids;
- The work surface provided with a slope or other means for directing spilled materials to the containment or drainage system; and
- An approved means of containing or directing spilled or leaked liquids to the drainage system.
Related Code Sections
2705.2.3.3 Semiconductor Fabrication Facilities, Drainage and Containment for HPM Liquids
Each workstation utilizing HPM liquids shall have all of the following: Drainage piping systems connected to a compatible system for disposition ...
2020 Minnesota State Fire Code > 27 Semiconductor Fabrication Facilities > 2705 Use and Handling > 2705.2 Fabrication Areas > 2705.2.3 Workstations > 2705.2.3.3 Drainage and Containment for HPM Liquids
2705.2.3.3 Semiconductor Fabrication Facilities, Drainage and Containment for HPM Liquids
Each workstation utilizing HPM liquids shall have all of the following: Drainage piping systems connected to a compatible system for disposition ...
Minnesota Fire Code 2015 > 27 Semiconductor Fabrication Facilities > 2705 Use and Handling > 2705.2 Fabrication Areas > 2705.2.3 Workstations > 2705.2.3.3 Drainage and Containment for HPM Liquids
2703.2.3 Semiconductor Fabrication Facilities, Additional Requirements for HPM Supply Piping
In addition to the requirements in Section 2703.2, HPM supply piping and tubing for HPM gases and liquids shall comply with this section ...
2020 Minnesota State Fire Code > 27 Semiconductor Fabrication Facilities > 2703 General Safety Provisions > 2703.2 Systems, Equipment and Processes > 2703.2.3 Additional Requirements for HPM Supply Piping
2703.2.3 Semiconductor Fabrication Facilities, Additional Requirements for HPM Supply Piping
In addition to the requirements in Section 2703.2, HPM supply piping and tubing for HPM gases and liquids shall comply with this section ...
Minnesota Fire Code 2015 > 27 Semiconductor Fabrication Facilities > 2703 General Safety Provisions > 2703.2 Systems, Equipment and Processes > 2703.2.3 Additional Requirements for HPM Supply Piping
415.10.6.1 Special Detailed Requirements Based on Use and Occupancy, HPM Having a Health-Hazard Ranking of 3 or 4
Systems supplying HPM liquids or gases having a health-hazard ranking of 3 or 4 shall be welded throughout, except for connections, to the systems ...
Minnesota Building Code 2015 > 4 Special Detailed Requirements Based on Use and Occupancy > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.10 Group H-5 > 415.10.6 Piping and Tubing > 415.10.6.1 HPM Having a Health-Hazard Ranking of 3 or 4