718.3.1 Draftstopping Materials
JUMP TO FULL CODE CHAPTER
Draftstopping materials shall not be less than 1/2-inch (12.7 mm) gypsum board, 3/8-inch (9.5 mm) wood structural panel, 3/8-inch (9.5 mm) particleboard, 1-inch (25-mm) nominal lumber, cement fiberboard, batts or blankets of mineral wool or glass fiber, or other approved materials adequately supported. The integrity of draftstops shall be maintained.
Related Code Sections
718.3.1 Fire and Smoke Protection Features, Draftstopping Materials
Draftstopping materials shall not be less than 1 / 2 -inch (12.7 mm) gypsum board, 3 / 8 -inch (9.5 mm) wood structural panel, 3 / 8 -inch (9.5 mm ...
2014 FBC - Building, 5th edition > 7 Fire and Smoke Protection Features > 718 Concealed Spaces > 718.3 Draftstopping in Floors > 718.3.1 Draftstopping Materials
718.3.1 Fire and Smoke Protection Features, Draftstopping Materials
Draftstopping materials shall be not less than 1 / 2 -inch (12.7 mm) gypsum board, 3 / 8 -inch (9.5 mm) wood structural panel, 3 / 8 -inch (9.5 mm ...
2017 FBC - Building, 6th edition > 7 Fire and Smoke Protection Features > 718 Concealed Spaces > 718.3 Draftstopping in Floors > 718.3.1 Draftstopping Materials
718.3.1 Fire and Smoke Protection Features, Draftstopping Materials
Draftstopping materials shall be not less than 1 / 2 -inch (12.7 mm) gypsum board, 3 / 8 -inch (9.5 mm) wood structural panel, 3 / 8 -inch (9.5 mm ...
2020 FBC - Building, 7th edition > 7 Fire and Smoke Protection Features > 718 Concealed Spaces > 718.3 Draftstopping in Floors > 718.3.1 Draftstopping Materials
718.4.1.1 Fire and Smoke Protection Features, Openings
Openings in the partitions shall be protected by self-closing doors with automatic latches constructed as required for the partitions ...
2020 FBC - Building, 7th edition > 7 Fire and Smoke Protection Features > 718 Concealed Spaces > 718.4 Draftstopping in Attics > 718.4.1 Draftstopping Materials > 718.4.1.1 Openings
R302.12.1 Building Planning, Materials
Draftstopping materials shall be not less than 1 / 2 -inch (12.7 mm) gypsum board, 3 / 8 -inch (9.5 mm) wood structural panels or other approved ...