The maximum area protected by draft curtains shall not exceed 2,000 sq. ft. (186 m2) or two slips or berths, whichever is smaller. Draft curtains shall not extend past the piling line. Draft curtains shall have a minimum depth of 4 feet (1219 mm) and shall not extend closer than 8 feet (2438 mm) to the walking surface of the pier.