For spaces with operable openings on two opposite sides of the space, the distance from the operable openings shall be not more than 5H, where H is the ceiling height. [ASHRAE 62.1:6.4.1.2]
Upcodes Diagrams

Related Code Sections

402.2.1.2 Ventilation Air, Double Side Opening
For spaces with operable openings on two opposite sides of the space, the distance from the operable openings shall be not more than 5H, where H ...