// CODE SNIPPET
A9.4.6.2 Double-Layer Roof
2021 Oregon Energy Efficiency Specialty Code (OEESC) > Normative Appendix A Rated R-Value of Insulation and Assembly U-factor, C-Factor, and F-Factor Determinations > A9 Determination of Alternate Assembly U-Factors, C-Factors, F-Factors, or Heat Capacities > A9.4 Calculation Procedures and Assumptions > A9.4.6 Metal Building U-factor Equations > A9.4.6.2 Double-Layer Roof
Go To Full Code Chapter
The U-factor of metal building roofs that are insulated with double layers of fiberglass insulation (see Figure A9.4.6.2-1) shall be calculated using the procedure outlined in this section. The procedure assumes the insulation is compressed over the purlin and there may be a thermal spacer block present.
There are six steps in the calculation process:
Step 1—Characterize the thermal conductivity of the fiberglass.
Step 2—Determine the U-factor for the insulation in the cavity.
Step 3—Determine the U-factor over the structural framing member.
Step 4—Area weight the U-factors calculated in Steps 2 and 3.
Step 5—Determine the U-factor from the finite element analysis results.
Step 6—Determine the U-factor for any continuous insulation if present.
Step 1: The thermal conductivity of the fiberglass batt insulation is represented by a thermal curve of the form in Equation A9.4-12:

where | ||
k | = | thermal conductivity, Btu/h•ft2•°F |
ρ | = | density, lb/ft3 |
A | = | 0.014917 |
B | = | 0.0004377 |
C | = | 0.0056897 |
Step 2: Assume the double-layer fiberglass batt forms a parabolic profile defined by Equation A9.4-13:

The presence of two layers of fiberglass adds complexity because each layer has distinct reference properties (see Table A9.4.6.1). As the double layers are compressed, the thickness of each layer needs to be determined by considering that each layer achieves the same compressive force. Instead of having a closed-form analytical solution that predicts the U-factor for the cavity, the double-layer system requires that the parabolic profile be numerically integrated. The compression of the double-layer system is presented in Figure A9.4.6.2-2.
The thickness of the second layer (Y2) is described by Equation A9.4-14:

where | ||
Yc | = | compressed thickness of the double layers, ft |
ρo1 | = | reference density of first layer, lb/ft3 |
ρo2 | = | reference density of second layer, lb/ft3 |
W1 | = | reference weight of first layer, lb/ft2 |
W2 | = | reference weight of second layer, lb/ft2 |
The solutions to Equation A9.4-14 are Equation A9.4-15a and A9.4-15b:

Select the smaller value of Y2,a and Y2,b as Y2. Y1 shall be calculated as the difference between Yc and Y2. Next, the R-values for the two compressed layers of insulation shall be calculated and converted to a U-factor. This process shall be repeated along the entire profile and the results numerically integrated using maximum 0.04167 ft increments.
It is important to note that Equation A9.4-14 does not apply when the two layers of insulation are the same material. In this case, each compressed layer has the same thickness, which simplifies the U-factor calculations. The numerical integration still needs to be completed to determine the Uco.
Step 3: Determine the U-factor over the structural framing member. The variable Yo represents the thickness of the thermal spacer block and the thickness of the compressed insulation. The density of the compressed insulation is determined by Equation A9.4-16:

where | ||
ρc | = | density of the compressed insulation over the framing member, lb/ft3 |
tc | = | thickness of the compressed insulation over the framing member, ft |
The thermal resistance of the compressed insulation is determined by Equation A9.4-17:

Determine the overall framing U-factor (Ufo) at the structural framing member, including the air film resistances, using Equation A9.4-18:

where | ||
Ufo | = | U-factor over the structural framing member, Btu/h•ft2•°F |
RTB | = | R-value of the thermal spacer block, h•ft2•°F/Btu |
Rc | = | R-value of the compressed insulation, h•ft2•°F/Btu |

where | ||
Ues | = | area-weighted U-factor for the entire system, Btu/h•ft2•°F |
Step 5: Calculate the adjusted overall U-factor (Uadj) using Equation A9.4-20:

where | ||
Uadj | = | adjusted overall U-factor represented by correlation with the finite element modeling, Btu/h•ft2•°F |
Step 6: If there is any continuous insulation present, calculate the overall U-factor using Equation A9.4-21:


Figure A9.4.6.2-1 Geometry of double layers of fiberglass batts.
where | ||
X | = | distance from edge of purlin or girt, ft |
Y | = | distance from edge of roof panel or wall panel, ft |
L | = | length from edge of purlin or girt to centerline of cavity, ft |
wf | = | width of purlin or girt flange, ft |
Yo | = | distance between purlin or girt and the roof panel or wall panel, ft |
Ym | = | distance from edge of roof panel or wall panel at the cavity centerline, ft |

Figure A9.4.6.2-2 Compression of double layers of fiberglass insulation.
Related Code Sections
A9.4.6.2 Normative Appendix A Rated R-Value of Insulation and Assembly U-factor, C-Factor, and F-Factor Determinations, Double-Layer Roof
The U-factor of metal building roofs that are insulated with double layers of fiberglass insulation (see Figure A9.4.6.2-1) shall be calculated using ...
2021 Oregon Energy Efficiency Specialty Code (OEESC) > Normative Appendix A Rated R-Value of Insulation and Assembly U-factor, C-Factor, and F-Factor Determinations > A9 Determination of Alternate Assembly U-Factors, C-Factors, F-Factors, or Heat Capacities > A9.4 Calculation Procedures and Assumptions > A9.4.6 Metal Building U-factor Equations > A9.4.6.2 Double-Layer Roof
A2.3.2.2 Normative Appendix A Rated R-Value of Insulation and Assembly U-factor, C-Factor, and F-Factor Determinations, Double Layer
is for unfaced insulation installed above the first layer and parallel to the purlins and then compressed when the metal roof panels are attached. A ...
A3.2.2.4 Normative Appendix A Rated R-Value of Insulation and Assembly U-factor, C-Factor, and F-Factor Determinations, Double-Layer
or adhered to the insulation, is installed inside of the girts to form a continuous layer. A thermal spacer block or thermal break strip between the girts ...
2021 Oregon Energy Efficiency Specialty Code (OEESC) > Normative Appendix A Rated R-Value of Insulation and Assembly U-factor, C-Factor, and F-Factor Determinations > A3 Above-Grade Walls > A3.2 Metal Building Walls > A3.2.2 Rated R-Value of Insulation for Metal Building Walls > A3.2.2.4 Double-Layer
719.4 Fire and Smoke Protection Features, Double Reinforcement
Plaster protection more than 1 inch (25 mm) in thickness shall be reinforced with an additional layer of approved lath embedded not less than 3/4 ...
A9.4 Normative Appendix A Rated R-Value of Insulation and Assembly U-factor, C-Factor, and F-Factor Determinations, Calculation Procedures and Assumptions
the assembly U-factor. For double-layer metal building roof systems, the calculation procedure outlined in Section A9.4.6.2 shall be used to calculate ...
2021 Oregon Energy Efficiency Specialty Code (OEESC) > Normative Appendix A Rated R-Value of Insulation and Assembly U-factor, C-Factor, and F-Factor Determinations > A9 Determination of Alternate Assembly U-Factors, C-Factors, F-Factors, or Heat Capacities > A9.4 Calculation Procedures and Assumptions