404.2.4.2 Doorways Without Doors or Gates, Sliding Doors, and Folding Doors
Go To Full Code Chapter
Doorways less than 36 inches (915 mm) wide without doors or gates, sliding doors, or folding doors shall have maneuvering clearances complying with Table 404.2.4.2.
Approach Direction | Minimum Maneuvering Clearance | |
---|---|---|
Perpendicular to Doorway | Parallel to Doorway (beyond stop/latch side unless noted) | |
| ||
From Front | 48 inches (1220 mm) | 0 inches (0 mm) |
From side1 | 42 inches (1065 mm) | 0 inches (0 mm) |
From pocket/hinge side | 42 inches (1065 mm) | 22 inches (560 mm)2 |
From stop/latch side | 42 inches (1065 mm) | 24 inches (610 mm) |
![]() |