1025.2.6 Doors Within the Exit Path
Go To Full Code Chapter
Doors through which occupants must pass in order to complete the exit path shall be provided with markings complying with Sections 1025.2.6.1 through 1025.2.6.3.
1025.2.6.1 Emergency Exit Symbol
The doors shall be identified by a low-location luminous emergency exit symbol complying with NFPA 170. The exit symbol shall be not less than 4 inches (102 mm) in height and shall be mounted on the door, centered horizontally, with the top of the symbol not higher than 18 inches (457 mm) above the finished floor.
1025.2.6.2 Door Hardware Markings
Door hardware shall be marked with not less than 16 square inches (10323 mm2) of luminous material. This marking shall be located behind, immediately adjacent to, or on the door handle or escutcheon. Where a panic bar is installed, such material shall be not less than 1 inch (25 mm) wide for the entire length of the actuating bar or touchpad.
1025.2.6.3 Door Frame Markings
The top and sides of the door frame shall be marked with a solid and continuous 1-inch- to 2-inch-wide (25 mm to 51 mm) stripe. Where the door molding does not provide sufficient flat surface on which to locate the stripe, the stripe shall be permitted to be located on the wall surrounding the frame.
Related Code Sections
1025.2.6 Means of Egress, Doors Within the Exit Path
Doors through which occupants must pass in order to complete the exit path shall be provided with markings complying with Sections 1025.2.6.1 through ...
1025.2.6 Means of Egress, Doors Within the Exit Path
Doors through which occupants must pass in order to complete the exit path shall be provided with markings complying with Sections 1025.2.6.1 through ...
1025.2.6.1 Means of Egress, Emergency Exit Symbol
The doors shall be identified by a low-location luminous emergency exit symbol complying with NFPA 170. The exit symbol shall be not less than 4 ...
1013.1 Means of Egress, Where Required
or the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs ...
1013.1 Means of Egress, Where Required
or the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs ...