1104.7 Doors—General
JUMP TO FULL CODE CHAPTER
Except where modified by Section 1008.1.2, doors shall be of the side-hinged swing type. Doors shall swing in the direction of egress travel when serving an occupant load of 50 or more persons. The minimum width of each door opening shall be sufficient for the occupant load thereof. Locks and latches shall comply with Sections 1008.1.9 through 1008.1.11.4.
Except where modified by this section, each required means of egress door shall comply with the minimum dimensions specified herein. Doors shall provide a clear width of not less than 28 inches (711 mm). Where this section requires a minimum clear width of 28 inches (711 mm) and a door opening includes two door leafs without a mullion, one leaf shall provide a clear opening width of 28 inches (711 mm). The maximum width of a swinging door leaf shall be 48 inches (1219 mm) nominal. The height of doors shall not be less than 80 inches (2032 mm).
Door openings to storage closets less than 10 square feet (0.93 m2) in area shall not be limited by the minimum width.
Width of door leafs in revolving doors shall not be limited.
Door openings within a dwelling unit are permitted to be 78 inches (1981 mm) in height.
The minimum clear width for doors in the means of egress from hospitals; nursing homes; limited-care facilities; psychiatric hospital sleeping rooms; and diagnostic and treatment areas, such as x-ray, surgery, or physical therapy, shall be not less than 32 inches (810 mm) wide. Existing 34-inch (865 mm) doors shall be permitted. Existing 28-inch (710 mm) corridor doors in facilities where the fire plans do not require evacuation by bed, gurney, or wheelchair shall be permitted.
Related Code Sections
1104.7 Construction Requirements for Existing Buildings, Doors—General
Except where modified by Section 1008.1.2, doors shall be of the side-hinged swing type. Doors shall swing in the direction of egress travel when ...
Minnesota Fire Code 2015 > 11 Construction Requirements for Existing Buildings > 1104 Means of Egress for Existing Buildings > 1104.7 Doors—General
1104.7.1.5 Construction Requirements for Existing Buildings, Health Care Facilities
The minimum clear width for doors in the means of egress from hospitals; nursing homes; limited-care facilities; psychiatric hospital sleeping ...
Minnesota Fire Code 2015 > 11 Construction Requirements for Existing Buildings > 1104 Means of Egress for Existing Buildings > 1104.7 Doors—General > 1104.7.1 Size of Doors > 1104.7.1.5 Health Care Facilities
402.8.8 Special Detailed Requirements Based on Occupancy and Use, Security Grilles and Doors
and grilles shall remain in the full open position during the period of occupancy by the general public. Doors or grilles shall not be brought ...
2020 Minnesota Building Code > 4 Special Detailed Requirements Based on Occupancy and Use > 402 Covered Mall and Open Mall Buildings > 402.8 Means of Egress > 402.8.8 Security Grilles and Doors
907.3.3 Fire Protection Systems, Door Hold-Open Functions
a general evacuation signal when the doors being held open are part of the means of egress corridor or stair system. Door hold-open smoke detectors ...
Minnesota Fire Code 2015 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Fire Safety Functions > 907.3.3 Door Hold-Open Functions
907.3.3 Fire Protection Systems, Door Hold-Open Functions
a general evacuation signal when the doors being held open are part of the means of egress corridor or stair system. Door hold-open smoke detectors ...
Minnesota Building Code 2015 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Fire Safety Functions > 907.3.3 Door Hold-Open Functions