7.2.1.4.2* Door Leaf Swing Direction
Go To Full Code Chapter
Door leaves required to be of the side-hinged or pivoted-swinging type shall swing in the direction of egress travel under any of the following conditions:
- Where serving a room or area with an occupant load of 50 or more, except under any of the following conditions:
- Door leaves in horizontal exits shall not be required to swing in the direction of egress travel where permitted by 7.2.4.3.8.1 or 7.2.4.3.8.2.
- Door leaves in smoke barriers shall not be required to swing in the direction of egress travel in existing health care occupancies, as provided in Chapter 19.
- Where the door assembly is used in an exit enclosure, unless the door opening serves an individual living unit that opens directly into an exit enclosure
- Where the door opening serves a high-hazard contents area
Related Code Sections
7.2.1.4.2* Means of Egress, Door Leaf Swing Direction
Door leaves required to be of the side-hinged or pivoted-swinging type shall swing in the direction of egress travel under any of the following ...
32.7.7 New Residential Board and Care Occupancies, Inspection of Door Openings
Door assemblies for which the door leaf is required to swing in the direction of egress travel shall be inspected and tested not less than annually ...
33.7.7 Existing Residential Board and Care Occupancies, Inspection of Door Openings
Door assemblies for which the door leaf is required to swing in the direction of egress travel shall be inspected and tested not less than annually ...
7.2.4 Means of Egress, Horizontal Exits
Where the bridge serves as a horizontal exit in one direction, the horizontal exit door leaf shall be required to swing only in the direction ...
7.2.1.4.3.2 Means of Egress,
When fully open, any door leaf in a means of egress shall not project more than 7 in. (180 mm) into the required width of an aisle, a corridor ...