[BE] 1010.1.9.10 Door Hardware Release of Electrically Locked Egress Doors
JUMP TO FULL CODE CHAPTER
Door hardware release of electric locking systems shall be permitted on doors in the means of egress in any occupancy except Group H, where installed and operated in accordance with all of the following:
- The door hardware that is affixed to the door leaf has an obvious method of operation that is readily operated under all lighting conditions.
- The door hardware is capable of being operated with one hand and shall comply with Section 1010.1.9.6.
- Operation of the door hardware directly interrupts the power to the electric lock and unlocks the door immediately.
- Loss of power to the electric locking system automatically unlocks the door.
- Where panic or fire exit hardware is required by Section 1010.1.10, operation of the panic or fire exit hardware also releases the electric lock.
- The locking system units shall be listed in accordance with UL 294.
Related Code Sections
1010.1.9.10 Means of Egress, Door Hardware Release of Electrically Locked Egress Doors
Door hardware release of electric locking systems shall be permitted on doors in the means of egress in any occupancy except Group H, where installed ...
California Fire Code 2019 > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.9 Door Operations > 1010.1.9.10 Door Hardware Release of Electrically Locked Egress Doors
1010.1.9.10 Means of Egress, Door Hardware Release of Electrically Locked Egress Doors
Door hardware release of electric locking systems shall be permitted on doors in the means of egress in any occupancy except Group H where ...
California Building Code 2019 (Vol 1 & 2) > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.9 Door Operations > 1010.1.9.10 Door Hardware Release of Electrically Locked Egress Doors
1010.1.10 Means of Egress, Panic and Fire Exit Hardware
not classified as an assembly occupancy E, I-2 or I-2.1 occupancies shall not be provided with a latch or lock other than panic hardware or fire exit ...
California Building Code 2016 (Vol 1 & 2) > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.10 Panic and Fire Exit Hardware
1010.1.10 Means of Egress, Panic and Fire Exit Hardware
not classified as an assembly occupancy, E, I-2 or I-2.1 occupancies shall not be provided with a latch or lock other than panic hardware or fire exit ...
California Fire Code 2016 > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.10 Panic and Fire Exit Hardware