Section 705 Door and Window Openings
JUMP TO FULL CODE CHAPTER
Where required when the building was originally constructed, opening protectives installed in fire-resistance-rated assemblies, smoke barriers and smoke partitions shall be inspected and maintained in accordance with this section.
Opening protectives in fire-resistance-rated assemblies shall be inspected and maintained in accordance with NFPA 80. Opening protectives in smoke barriers shall be inspected and maintained in accordance with NFPA 80 and NFPA 105. Openings in smoke partitions shall be inspected and maintained in accordance with NFPA 105. Fire doors and smoke and draft control doors shall not be blocked, obstructed, or otherwise made inoperable. Fusible links shall be replaced promptly whenever fused or damaged. Opening protectives and smoke and draft control doors shall not be modified.
Where approved by the fire code official, the application of field-applied labels associated with the maintenance of opening protectives shall follow the requirements of the approved third-party certification organization accredited for listing the opening protective.
Where required by the fire code official, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch (25 mm) high to read as follows:
Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.
Swinging fire doors shall close from the full-open position and latch automatically.
Horizontal and vertical sliding and rolling fire doors shall be inspected and tested annually to confirm proper operation and full closure. Records of inspections and testing shall be maintained.
Related Code Sections
Section 705 Fire and Smoke Protection Features, Door and Window Openings
inoperable. Fusible links shall be replaced promptly whenever fused or damaged. Opening protectives and smoke and draft control doors shall ...
705.2.5 Fire and Smoke Protection Features, Smoke- And Heat-Activated Doors
Smoke-activated doors shall be maintained to self-close or automatically close upon detection of smoke. Existing fusible-link-type automatic door ...
California Fire Code 2019 > 7 Fire and Smoke Protection Features > 705 Door and Window Openings > 705.2 Inspection and Maintenance > 705.2.5 Smoke- And Heat-Activated Doors
705.2.1 Fire and Smoke Protection Features, Labeling Requirements
Where approved by the fire code official, the application of field-applied labels associated with the maintenance of opening protectives shall follow ...
California Fire Code 2019 > 7 Fire and Smoke Protection Features > 705 Door and Window Openings > 705.2 Inspection and Maintenance > 705.2.1 Labeling Requirements
705.2.6 Fire and Smoke Protection Features, Testing
Horizontal and vertical sliding and rolling fire doors shall be inspected and tested annually to confirm proper operation and full closure. Records ...
California Fire Code 2019 > 7 Fire and Smoke Protection Features > 705 Door and Window Openings > 705.2 Inspection and Maintenance > 705.2.6 Testing