1102.2 Dome Strainers Required
Go To Full Code Chapter
Roof drains shall have domed strainers.
Exception: Roof drain strainers for use on sun decks, parking decks, and similar areas that are normally serviced and maintained, shall be permitted to be of the flat surface type. Such roof drain strainers shall be level with the deck.
Upcodes Diagrams
Related Code Sections
1102.2 Storm Drainage, Dome Strainers Required
Roof drains shall have domed strainers. Exception: Roof drain strainers for use on sun decks, parking decks, and similar areas that are normally ...
22.21.2.6 Special Occupancy Requirements, Strainers
Strainers shall be required for systems utilizing discharge devices with waterways of less than 3/8 in. (9.5 mm) diameter. [214:5.2.7] ...
26.21.2.6 Special Occupancy Requirements, Strainers
Strainers shall be required for systems utilizing discharge devices with waterways of less than 3/8 in. (9.5 mm) diameter. [214:5.2.7] ...
8.15.13.4 Installation Requirements, Strainers
A listed line strainer shall be installed in the main water supply preceding sprinklers having nominal K-factors smaller than K-2.8 (40) ...
7.9.10 System Requirements, Strainers
A listed line strainer shall be installed in the main water supply preceding sprinklers or automatic spray nozzles having nominal K-factors smaller ...