R602.12.6 Distribution of Braced Wall Panels
JUMP TO FULL CODE CHAPTER

Braced wall panels shall be distributed in accordance with the following requirements as shown in Figure R602.12.6.
- The edge of a braced wall panel shall be no more than 12 feet (3658 mm) from any building corner or rectangle corner.
- The distance between adjacent edges of braced wall panels shall be no more than 20 feet (6096 mm).
- Segments of exterior walls greater than 8 feet (2438 mm) in length shall have a minimum of one braced wall panel.
- Segments of exterior wall 8 feet (2438 mm) or less in length shall be permitted to have no braced wall panels.

For SI: 1 foot = 304.8 mm.
FIGURE R602.12.6
PANEL DISTRIBUTION
Braced wall panels shall be placed on each side of each story adjacent to balloon framed walls designed in accordance with Section R602.3 with a maximum height of two stories.
Related Code Sections
R602.12.6 Wall Construction, Distribution of Braced Wall Panels
Braced wall panels shall be distributed in accordance
with the following requirements as shown in Figure
R602.12.6.
The edge of a braced wall ...
2015 Virginia Residential Code > 6 Wall Construction > R602 Wood Wall Framing > R602.12 Practical Wall Bracing > R602.12.6 Distribution of Braced Wall Panels
R602.12.6 Wall Construction, Distribution of Braced Wall Panels
Braced wall panels shall be distributed in accordance with the following requirements as shown in Figure R602.12.6. The edge of a braced wall ...
2012 Virginia Residential Code > 6 Wall Construction > R602 Wood Wall Framing > R602.12 Practical Wall Bracing > R602.12.6 Distribution of Braced Wall Panels
R602.12.6 Wall Construction, Distribution of Braced Wall Panels
Braced wall panels shall be distributed in accordance with the following requirements as shown in Figure R602.12.6: The edge of a braced wall ...
2018 Virginia Residential Code > 6 Wall Construction > R602 Wood Wall Framing > R602.12 Practical Wall Bracing > R602.12.6 Distribution of Braced Wall Panels
R602.12.6.1 Wall Construction, Panels Adjacent to Balloon Framed Walls
Braced wall panels shall be placed on each side
of each story adjacent to balloon framed walls
designed in accordance with Section R602.3 ...
2015 Virginia Residential Code > 6 Wall Construction > R602 Wood Wall Framing > R602.12 Practical Wall Bracing > R602.12.6 Distribution of Braced Wall Panels > R602.12.6.1 Panels Adjacent to Balloon Framed Walls
A304.4.2 Prescriptive Provisions for Seismic Strengthening of Cripple Walls and Sill Plate Anchorage of Light, Wood-Frame Residential Buildings, Distribution and Amount of Bracing
See Table A3-A and Figure A3-10 for the distribution and amount of bracing required for each wall line. Each braced panel length must be at least two ...
2015 Virginia Existing Building Code (USBC, Part II) > A3 Prescriptive Provisions for Seismic Strengthening of Cripple Walls and Sill Plate Anchorage of Light, Wood-Frame Residential Buildings > A304 Strengthening Requirements > A304.4 Cripple Wall Bracing > A304.4.2 Distribution and Amount of Bracing