6204.1.2 Distance From Detached Buildings to Exposures
Go To Full Code Chapter
In addition to the requirements of the International Building Code, detached storage buildings for Class I, II, III, IV and V organic peroxides shall be located in accordance with Table 6204.1.2. Detached buildings containing quantities of unclassified detonable organic peroxides in excess of those set forth in Table 5003.8.2 shall be located in accordance with Table 5604.5.2(1).
TABLE 6204.1.2
ORGANIC PEROXIDES—DISTANCE TO EXPOSURES FROM DETACHED STORAGE BUILDINGS OR OUTDOOR STORAGE AREASORGANIC PEROXIDE CLASS | MAXIMUM STORAGE QUANTITY (POUNDS) AT MINIMUM SEPARATION DISTANCE | |||||
Distance to buildings, lot lines, public streets, public alleys, public ways or means of egress | Distance between individual detached storage buildings or individual outdoor storage areas | |||||
50 feet | 100 feet | 150 feet | 20 feet | 75 feet | 100 feet | |
I | 2,000 | 20,000 | 175,000 | 2,000 | 20,000 | 175,000 |
II | 100,000 | 200,000 | No Limit | 100,000a | No Limit | No Limit |
III | 200,000 | No Limit | No Limit | 200,000a | No Limit | No Limit |
IV | No Limit | No Limit | No Limit | No Limit | No Limit | No Limit |
V | No Limit | No Limit | No Limit | No Limit | No Limit | No Limit |
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.
- Where the amount of organic peroxide stored exceeds this amount, the minimum separation shall be 50 feet.
Related Code Sections
6204.1.2 Organic Peroxides, Distance From Detached Buildings to Exposures
set forth in Table 5003.8.2 shall be located in accordance with Table 5604.5.2(1). TABLE 6204.1.2 ORGANIC PEROXIDES—DISTANCE TO EXPOSURES FROM ...
6204.1.2 Organic Peroxides, Distance From Detached Buildings to Exposures
set forth in Table 5003.8.2 shall be located in accordance with Table 5604.5.2(1). TABLE 6204.1.2 ORGANIC PEROXIDES—DISTANCE TO EXPOSURES FROM ...
R301.2.1.4 Building Planning, Exposure Category
generally less than 30 feet (9144 mm) extending more than 1,500 feet (457 m) from the building site in any quadrant. This exposure shall apply to any ...
7.8.3 Compressed Gases, Distance to Exposures
The outdoor storage or use of pyrophoric compressed gas shall be in accordance with Table 7.8.3. Table 7.8.3 Distance to Exposures for Pyrophoric ...