3406.4.5.6 Distance From Aboveground Tanks to Exposures
JUMP TO FULL CODE CHAPTER
No aboveground tank shall be installed within:
- 1,000 feet (304 800 mm) of the nearest wall of a building occupied as a school or hospital, or an entrance to or exit from a tunnel for motor vehicles, subway or railroad trains, or the ventilating buildings or shafts of such tunnels.
- 250 feet (76 200 mm) of any point under a bridge for pedestrians, motor vehicles, subway or railroad trains, a public park or a land zoned for residential purposes.
Related Code Sections
§27-440 Special Uses and Occupancies, Gasoline and Diesel Oil Motor Vehicle Fuel Storage
of this chapter. (c) Tanks shall be located so that the forces from any building foundation and support loads are not transmitted to the tanks. The distance ...
NYC 1968 Code (Vol I) > 7 Special Uses and Occupancies > 8 Automotive Service Stations > §27-440 Gasoline and Diesel Oil Motor Vehicle Fuel Storage
704.10 Fire-Resistance-Rated Construction, Vertical Exposure
hour for a minimum distance of 10 feet (3048 mm) from the adjoining building and the entire length and span of the supporting elements for the fire ...
NYC Building Code 2008 > 7 Fire-Resistance-Rated Construction > 704 Exterior Walls > 704.10 Vertical Exposure
1609.4 Structural Design, Exposure Category
roughness within each 45-degree (0.79 rad) sector shall be determined for a distance upwind of the site as defined in Section 1609.4.3 from ...
1609.4 Structural Design, Exposure Category
topography and vegetation as well as from constructed features. When applying the simplified wind load method of Section 1609.6, a single exposure category ...
705.8.6 Fire and Smoke Protection Features, Vertical Exposure
for a minimum distance of 10 feet (3048 mm) from the exterior wall facing the imaginary line and the entire length and span of the supporting elements ...
NYC Building Code 2014 > 7 Fire and Smoke Protection Features > 705 Exterior Walls > 705.8 Openings > 705.8.6 Vertical Exposure