// CODE SNIPPET
5606.5.1 Display
JUMP TO FULL CODE CHAPTER
Display of small arms ammunition components in Group M occupancies shall comply with Sections 5606.5.1.1 through 5606.5.1.3.
Not more than 20 pounds (9 kg) of smokeless propellants, in containers of 1 pound (0.454 kg) or less capacity each, shall be displayed in Group M occupancies.
No more than 1 pound (0.454 kg) of black powder shall be displayed in Group M occupancies.
No more than 10,000 small arms primers shall be displayed in Group M occupancies.
Related Code Sections
5606.5.1 Explosives and Fireworks, Display
Display of small arms ammunition components in Group M occupancies shall comply with Sections 5606.5.1.1 through 5606.5.1.3 ...
2020 Minnesota State Fire Code > 56 Explosives and Fireworks > 5606 Small Arms Ammunition and Small Arms Ammunition Components > 5606.5 Display and Storage in Group M Occupancies > 5606.5.1 Display
5606.5.1 Explosives and Fireworks, Display
Display of small arms ammunition components in Group M occupancies shall comply with Sections 5606.5.1.1 through 5606.5.1.3 ...
Minnesota Fire Code 2015 > 56 Explosives and Fireworks > 5606 Small Arms Ammunition and Small Arms Ammunition Components > 5606.5 Display and Storage in Group M Occupancies > 5606.5.1 Display
5608.1.1 Explosives and Fireworks, Displays
Permits are required to conduct a fireworks display. A fireworks display is only permitted when supervised by a pyrotechnic operator certified ...
Minnesota Fire Code 2015 > 56 Explosives and Fireworks > 5608 Fireworks Display > 5608.1 General > 5608.1.1 Displays
6503.1 Pyroxylin (Cellulose Nitrate) Plastics, Displays
Tables shall be spaced not less than 3 feet (914 mm) apart. Where articles are displayed on counters, they shall be arranged in a like manner ...
2020 Minnesota State Fire Code > 65 Pyroxylin (Cellulose Nitrate) Plastics > 6503 General Requirements > 6503.1 Displays
6503.1 Pyroxylin (Cellulose Nitrate) Plastics, Displays
Tables shall be spaced at least 3 feet (914 mm) apart. Where articles are displayed on counters, they shall be arranged in a like manner ...
Minnesota Fire Code 2015 > 65 Pyroxylin (Cellulose Nitrate) Plastics > 6503 General Requirements > 6503.1 Displays