In multilevel assembly seating areas, wheelchair spaces shall be provided on the main floor level and on one of each two additional floor or mezzanine levels. Wheelchair spaces shall be provided in each luxury box, club box and suite within assembly facilities.
Exceptions:
  1. In multilevel assembly seating areas utilized for worship services where the second floor or mezzanine level contains 25 percent or less of the total seating capacity, wheelchair spaces shall be permitted to all be located on the main level.
  2. In multilevel assembly seating areas where the second floor or mezzanine level provides 25 percent or less of the total seating capacity and 300 or fewer seats, all wheelchair spaces shall be permitted to be located on the main level.
  3. Wheelchair spaces in team or player seating serving areas of sport activity are not required to be dispersed.

Related Code Sections

802.10 Special Rooms and Spaces, Wheelchair Space Dispersion
shall not be required. TABLE 802.10 WHEELCHAIR SPACE LOCATION DISPERSION Total seating in Assembly Areas Minimum required number ...
221.2 Scoping Requirements, Wheelchair Spaces
Wheelchair spaces complying with 221.2 shall be provided in assembly areas with fixed seating ...
802.10.1 Special Rooms and Spaces, Horizontal Dispersion
: Horizontal dispersion shall not be required in assembly areas with 300 or fewer seats if the wheelchair space locations are located within the 2nd and 3rd ...