[F] 415.5.2 Dispensing, Use and Handling
JUMP TO FULL CODE CHAPTER
Where hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704 are transported through corridors, interior exit stairways or ramps, or exit passageways, there shall be an emergency telephone system, a local manual alarm station or an approved alarm-initiating device at not more than 150-foot (45 720 mm) intervals and at each exit and exit access doorway throughout the transport route. The signal shall be relayed to an approved central, proprietary or remote station service or constantly attended on-site location and shall initiate a local audible alarm.
Related Code Sections
415.5.2 Special Detailed Requirements Based on Use and Occupancy, Dispensing, Use and Handling
Where hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704 are transported through corridors, interior exit stairways ...
Los Angeles Building Code > 4 Special Detailed Requirements Based on Use and Occupancy > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.5 Emergency Alarms > 415.5.2 Dispensing, Use and Handling
415.5.2 Special Detailed Requirements Based on Occupancy and Use, Dispensing, Use and Handling
Where hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704 are transported through corridors, interior exit stairways ...
Los Angeles Building Code > 4 Special Detailed Requirements Based on Occupancy and Use > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.5 Emergency Alarms > 415.5.2 Dispensing, Use and Handling
5005.4.4 Hazardous Materials—General Provisions, Dispensing, Use and Handling
Where hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704 are transported through corridors, interior exit stairways ...
2017 LA City Fire Code > 50 Hazardous Materials—General Provisions > 5005 Use, Dispensing and Handling > 5005.4 Handling > 5005.4.4 Dispensing, Use and Handling
Section 5705 Flammable and Combustible Liquids, Dispensing, Use, Mixing and Handling
Dispensing, use, mixing and handling of flammable liquids shall be in accordance with Section 5703 and this section. Tank vehicle and tank car ...
2017 LA City Fire Code > 57 Flammable and Combustible Liquids > 5705 Dispensing, Use, Mixing and Handling
5003.9.2 Hazardous Materials—General Provisions, Security
Storage, dispensing, use and handling areas shall be secured against unauthorized entry and safeguarded in a manner approved by the fire code ...
2017 LA City Fire Code > 50 Hazardous Materials—General Provisions > 5003 General Requirements > 5003.9 General Safety Precautions > 5003.9.2 Security