1910.106(g)(3)(iv) Dispensing Units
JUMP TO FULL CODE CHAPTER
Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall be transferred from tanks by means of fixed pumps so designed and equipped as to allow control of the flow and to prevent leakage or accidental discharge.
Only listed devices may be used for dispensing Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C). No such device may be used if it shows evidence of having been dismantled.
Every dispensing device for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), installed after December 31, 1978, shall contain evidence of listing so placed that any attempt to dismantle the device will result in damage to such evidence, visible without disassembly or dismounting of the nozzle.
Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall not be dispensed by pressure from drums, barrels, and similar containers. Approved pumps taking suction through the top of the container or approved self-closing faucets shall be used.
The dispensing units, except those attached to containers, shall be mounted either on a concrete island or protected against collision damage by suitable means.
Related Code Sections
1910.106(g)(3)(iv) Hazardous Materials, Dispensing Units
The dispensing units, except those attached to containers, shall be mounted either on a concrete ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(g) Service Stations > 1910.106(g)(3) Dispensing Systems > 1910.106(g)(3)(iv) Dispensing Units
1910.106(g)(3)(ii) Hazardous Materials, Inside Location
Approved dispensing units may be located inside of buildings. The dispensing area shall be separated from other areas in an approved manner. The ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(g) Service Stations > 1910.106(g)(3) Dispensing Systems > 1910.106(g)(3)(ii) Inside Location
1910.106(g)(4)(i) Hazardous Materials, Dispensing
Dispensing shall be by approved dispensing units with or without integral pumps and may be located ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(g) Service Stations > 1910.106(g)(4) Marine Service Stations > 1910.106(g)(4)(i) Dispensing
1910.106(g)(3) Hazardous Materials, Dispensing Systems
The dispensing units, except those attached to containers, shall be mounted either on a concrete island or protected against collision ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(g) Service Stations > 1910.106(g)(3) Dispensing Systems
1910.106(g)(3)(v)(d) Hazardous Materials,
A control shall be provided that will permit the pump to operate only when a dispensing nozzle is removed from its bracket on the dispensing unit ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(g) Service Stations > 1910.106(g)(3) Dispensing Systems > 1910.106(g)(3)(v) Remote Pumping Systems > 1910.106(g)(3)(v)(d)