(k) 3406.4.11 Dispensing From Bulk Plants Prohibited
JUMP TO FULL CODE CHAPTER
The dispensing of flammable or combustible liquids from aboveground bulk storage tanks located at a bulk plant shall be prohibited.
Exception: The dispensing of diesel fuel at a terminal or bulk plant into a motor vehicle that is transporting petroleum products or equipment essential to the operation of the terminal or bulk plant, provided that the motor vehicle is owned or leased by or operated under a contract with a person who has been issued a motor fuel dealers license under section 5735.02 of the Revised Code. For such dispensing, the provisions of this rule governing capacity limitations shall not apply.
Aboveground storage tanks and associated dispensers utilized for dispensing purposes at a fleet vehicle motor fuel dispensing facility located at a bulk plant shall be separated from bulk plant operations (bulk tanks and loading racks) by a minimum of 100 feet.
The dispensing tanks and dispensers shall be installed in compliance with paragraphs (D)(3404) and (E)(3405) of this rule.
The individual capacity of the tanks shall not exceed 12,000 gallons and the aggregate capacity shall not exceed 48,000 gallons. Dispensing areas containing the maximum aggregate capacity shall be separated from each other and the bulk plant operations by a minimum of 100 feet.
At a property that contains a fleet vehicle motor fuel dispensing facility, the public may access the property but shall be prohibited from the fleet vehicle facility.
Related Code Sections
3406.4.11 Ohio Administrative Code 1301:7-7-34 Flammable and Combustible Liquids, Dispensing From Bulk Plants Prohibited
The dispensing of flammable or combustible liquids from aboveground bulk storage tanks located at a bulk plant shall be prohibited. Exception ...
Ohio Fire Code 2011 > Ohio Administrative Code 1301:7-7-34 Flammable and Combustible Liquids > 3406 Special Operations > 3406.4 Bulk Plants or Terminals > 3406.4.11 Dispensing From Bulk Plants Prohibited
3404.1.1 Ohio Administrative Code 1301:7-7-34 Flammable and Combustible Liquids,
: 1. At a bulk plant or terminal, the public may access the facility premises but shall be prohibited from the bulk storage and transfer operation ...
Ohio Fire Code 2011 > Ohio Administrative Code 1301:7-7-34 Flammable and Combustible Liquids > 3404 Storage > 3404.1 General > 3404.1.1
3404.1 Ohio Administrative Code 1301:7-7-34 Flammable and Combustible Liquids, General
: 1. At a bulk plant or terminal, the public may access the facility premises but shall be prohibited from the bulk storage and transfer operation ...
Ohio Fire Code 2011 > Ohio Administrative Code 1301:7-7-34 Flammable and Combustible Liquids > 3404 Storage > 3404.1 General
2212 Ohio Administrative Code 1301:7-7-22 Motor Fuel-Dispensing Facilities and Repair Garages, Service Station at a Bulk Plant or Terminal
That portion of a bulk plant property where flammable or combustible liquids are stored and dispensed from fixed equipment into the fuel tanks ...
Ohio Fire Code 2011 > Ohio Administrative Code 1301:7-7-22 Motor Fuel-Dispensing Facilities and Repair Garages > 2212 Service Station at a Bulk Plant or Terminal
2212.1 Ohio Administrative Code 1301:7-7-22 Motor Fuel-Dispensing Facilities and Repair Garages, General
That portion of a bulk plant property where flammable or combustible liquids are stored and dispensed from fixed equipment into the fuel tanks ...
Ohio Fire Code 2011 > Ohio Administrative Code 1301:7-7-22 Motor Fuel-Dispensing Facilities and Repair Garages > 2212 Service Station at a Bulk Plant or Terminal > 2212.1 General