2209.1.5 Dispensing Area Signage
JUMP TO FULL CODE CHAPTER
Durable signs shall be conspicuously posted in dispensing areas in hydrogen motor fuel-dispensing facilities in compliance with the requirements of FC 2209.1.5.1 through 2209.1.5.4.
A sign setting forth dispenser operating instructions shall be posted on every dispenser. Such sign shall also indicate the location of the emergency shutdown valves and emergency shutdown controls required by FC 2209.7.3 and 2209.7.4.
A warning sign that reads as follows shall be posted on or immediately adjacent to each dispenser:
- No smoking.
- Shut off engine.
A sign setting forth emergency procedures that reads as follows shall be posted in the dispensing area, or other location designated in this section:
IN CASE OF FIRE, LEAK OR EMERGENCY:
ACTIVATE EMERGENCY SHUTDOWN
DIRECT VEHICLE OCCUPANTS
TO EXIT VEHICLES AND
LEAVE AREA IMMEDIATELY
KEEP ALL PERSONS AWAY FROM THE AREA
NOTIFY THE FIRE DEPARTMENT (CALL 911)
(FACILITY ADDRESS)
(indicate address, with cross-street reference).
IN CASE OF FIRE, LEAK OR EMERGENCY:
ACTIVATE EMERGENCY SHUTDOWN
DIRECT VEHICLE OCCUPANTS
TO EXIT VEHICLES AND
LEAVE AREA IMMEDIATELY
KEEP ALL PERSONS AWAY FROM THE AREA
NOTIFY THE FIRE DEPARTMENT (CALL 911)
(FACILITY ADDRESS)
(indicate address, with cross-street reference).
An approved sign having 2-inch (51-mm) block letters shall be conspicuously posted at approved locations on the exterior of any canopy structure when gaseous hydrogen compression and storage equipment is located on top of such canopy reading "CANOPY TOP HYDROGEN STORAGE."
Related Code Sections
1007.9 Means of Egress, Signage
Signage indicating special accessibility provisions shall be provided as shown: Each door providing access to an area of rescue assistance from ...
Section 1110 Accessibility, Signage
Signage indicating special accessibility provisions shall be provided as follows:
Each assembly area ...
Section 1110 Accessibility, Signage
discharge, signage shall be provided in accordance with Section 1011.3.
At areas of rescue assistance, signage shall be provided in accordance ...
Section E107 Supplementary Accessibility Requirements, Signage
that are not located at the door to the space they serve are not required to comply. Building directories, menus, seat and row designations in assembly areas ...
Section E107 Supplementary Accessibility Requirements, Signage
in assembly areas, occupant names, building addresses and company names and logos are not required to comply.
Signs in parking facilities are not required ...