// CODE SNIPPET
2306.7.4 Dispenser Emergency Shutoff Valve
JUMP TO FULL CODE CHAPTER
An approved automatic emergency shutoff valve designed to close in the event of a fire or impact shall be properly installed in the liquid supply line at the base of each dispenser supplied by a remote pump. The valve shall be installed so that the shear groove is flush with or within 1/2 inch (12.7 mm) of the top of the concrete dispenser island and there is clearance provided for maintenance purposes around the valve body and operating parts. The valve shall be installed at the liquid supply line inlet of each overhead-type dispenser. Where installed, a vapor return line located inside the dispenser housing shall have a shear section or approved flexible connector for the liquid supply line emergency shutoff valve to function. Emergency shutoff valves shall be installed and maintained in accordance with the manufacturer's instructions, tested at the time of initial installation and not less than yearly thereafter in accordance with Section 2305.2.4.
Related Code Sections
2306.7.4 Motor Fuel-Dispensing Facilities and Repair Garages, Dispenser Emergency Shutoff Valve
the dispenser housing shall have a shear section or approved flexible connector for the liquid supply line emergency shutoff valve to function ...
2017 LA City Fire Code > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2306 Flammable and Combustible Liquid Motor Fuel-Dispensing Facilities > 2306.7 Fuel-Dispensing Systems for Flammable or Combustible Liquids > 2306.7.4 Dispenser Emergency Shutoff Valve
2305.2 Motor Fuel-Dispensing Facilities and Repair Garages, Equipment Maintenance and Inspection
shutoff valve at the dispenser, where installed, shall be closed. Vehicle traffic and unauthorized persons shall be prevented from coming within 12 ...
2017 LA City Fire Code > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2305 Operational Requirements > 2305.2 Equipment Maintenance and Inspection
2307.6.1 Motor Fuel-Dispensing Facilities and Repair Garages, Product Control Valves
and dispensing unit mounted on a common base. An excess flow-control check valve or an emergency shutoff valve shall be installed ...
2017 LA City Fire Code > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2307 Liquefied Petroleum Gas Motor Fuel-Dispensing Facilities > 2307.6 Installation of LP-gas Dispensing Devices and Equipment > 2307.6.1 Product Control Valves
2309.5.2.1 Motor Fuel-Dispensing Facilities and Repair Garages, Identification
Manual emergency shutoff valves shall be identified and the location shall be clearly visible, accessible and indicated by means of a sign ...
2017 LA City Fire Code > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2309 Hydrogen Motor Fuel-Dispensing and Generation Facilities > 2309.5 Safety Precautions > 2309.5.2 Emergency Shutoff Valves > 2309.5.2.1 Identification
2309.5 Motor Fuel-Dispensing Facilities and Repair Garages, Safety Precautions
A manual emergency shutoff valve shall be provided to shut down the flow of gas from the hydrogen supply ...
2017 LA City Fire Code > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2309 Hydrogen Motor Fuel-Dispensing and Generation Facilities > 2309.5 Safety Precautions