1910.306(b)(2) Disconnecting Means for Cranes and Monorail Hoists
JUMP TO FULL CODE CHAPTER
Except as provided in paragraph (b)(2)(iv) of this section, a motor-circuit switch, molded case switch, or circuit breaker shall be provided in the leads from the runway contact conductors or other power supply on all cranes and monorail hoists.
Means shall be provided at the operating station to open the power circuit to all motors of the crane or monorail hoist where the disconnecting means is not readily accessible from the crane or monorail hoist operating station.
The disconnecting means may be omitted where a monorail hoist or hand-propelled crane bridge installation meets all of the following conditions:
The unit is controlled from the ground or floor level;
The unit is within view of the power supply disconnecting means; and
No fixed work platform has been provided for servicing the unit.
The disconnecting means shall be capable of being locked in the open position.
Related Code Sections
1910.306(b)(2) Electrical, Disconnecting Means for Cranes and Monorail Hoists
or monorail hoist where the disconnecting means is not readily accessible from the crane or monorail hoist operating station ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(b) Cranes and Hoists > 1910.306(b)(2) Disconnecting Means for Cranes and Monorail Hoists
1910.306(b)(2)(iv)(A) Electrical,
The unit is controlled from the ground or floor level ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(b) Cranes and Hoists > 1910.306(b)(2) Disconnecting Means for Cranes and Monorail Hoists > 1910.306(b)(2)(iv) > 1910.306(b)(2)(iv)(A)
1910.306(b)(2)(iv)(C) Electrical,
No fixed work platform has been provided for servicing the unit ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(b) Cranes and Hoists > 1910.306(b)(2) Disconnecting Means for Cranes and Monorail Hoists > 1910.306(b)(2)(iv) > 1910.306(b)(2)(iv)(C)
1910.306(b) Electrical, Cranes and Hoists
of the crane or monorail hoist where the disconnecting means is not readily accessible from the crane or monorail hoist operating station ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(b) Cranes and Hoists
1910.306 Electrical, Specific Purpose Equipment and Installations
circuit to all motors of the crane or monorail hoist where the disconnecting means is not readily accessible from the crane or monorail hoist operating ...