413.9 Discharge of CNG From Motor Vehicle Fuel Storage Containers
JUMP TO FULL CODE CHAPTER
The discharge of CNG from motor vehicle fuel cylinders for the purposes of maintenance, cylinder certification, calibration of dispensers or other activities shall be in accordance with this section. The discharge of CNG from motor vehicle fuel cylinders shall be accomplished through a closed transfer system or an approved method of atmospheric venting in accordance with Section 413.9.1 or 413.9.2.
A documented procedure that explains the logical sequence for discharging the cylinder shall be provided to the code official for review and approval. The procedure shall include what actions the operator will take in the event of a low-pressure or high-pressure natural gas release during the discharging activity. A drawing illustrating the arrangement of piping, regulators and equipment settings shall be provided to the code official for review and approval. The drawing shall illustrate the piping and regulator arrangement and shall be shown in spatial relation to the location of the compressor, storage vessels and emergency shutdown devices.
A drawing illustrating the location of the vessel support, piping, the method of grounding and bonding, and other requirements specified herein shall be provided to the code official for review and approval.
A method of rigidly supporting the vessel during the venting of CNG shall be provided. The selected method shall provide not less than two points of support and shall prevent horizontal and lateral movement of the vessel. The system shall be designed to prevent movement of the vessel based on the highest gas-release velocity through valve orifices at the vessel's rated pressure and volume. The structure or appurtenance shall be constructed of noncombustible materials.
The structure or appurtenance used for stabilizing the cylinder shall be separated from the site equipment, features and exposures and shall be located in accordance with Table 413.9.2.3.
EQUIPMENT OR FEATURE | MINIMUM SEPARATION (feet) |
Buildings | 25 |
Building openings | 25 |
Lot lines | 15 |
Public ways | 15 |
Vehicles | 25 |
CNG compressor and storage vessels | 25 |
CNG dispensers | 25 |
For SI: 1 foot = 304.8 mm.
The structure or appurtenance used for supporting the cylinder shall be grounded in accordance with NFPA 70. The cylinder valve shall be bonded prior to the commencement of venting operations.
A vent tube that will divert the gas flow to the atmosphere shall be installed on the cylinder prior to the commencement of the venting and purging operation. The vent tube shall be constructed of pipe or tubing materials approved for use with CNG in accordance with the International Fire Code.
The vent tube shall be capable of dispersing the gas not less than 10 feet (3048 mm) above grade level. The vent tube shall not be provided with a rain cap or other feature that would limit or obstruct the gas flow.
At the connection fitting of the vent tube and the CNG cylinder, a listed bidirectional detonation flame arrester shall be provided.
The vent tube shall be capable of dispersing the gas not less than 10 feet (3048 mm) above grade level. The vent tube shall not be provided with a rain cap or other feature that would limit or obstruct the gas flow.
At the connection fitting of the vent tube and the CNG cylinder, a listed bidirectional detonation flame arrester shall be provided.
Approved NO SMOKING signs shall be posted within 10 feet (3048 mm) of the cylinder support structure or appurtenance. Approved CYLINDER SHALL BE BONDED signs shall be posted on the cylinder support structure or appurtenance.
Related Code Sections
2308.8 Motor Fuel-Dispensing Facilities and Repair Garages, Discharge of CNG From Motor Vehicle Fuel Storage Containers
The discharge of CNG from motor vehicle fuel cylinders for the purposes of maintenance, cylinder certification, calibration of dispensers or other ...
Fire Code 2018 of Utah > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2308 Compressed Natural Gas Motor Fuel-Dispensing Facilities > 2308.8 Discharge of CNG From Motor Vehicle Fuel Storage Containers
413.9 Gas Piping Installations, Discharge of CNG From Motor Vehicle Fuel Storage Containers
The discharge of CNG from motor vehicle fuel cylinders for the purposes of maintenance, cylinder certification, calibration of dispensers or other ...
Fuel Gas Code 2018 of Utah > 4 Gas Piping Installations > 413 (IFGC) Compressed Natural Gas Motor Vehicle Fuel-Dispensing Facilities > 413.9 Discharge of CNG From Motor Vehicle Fuel Storage Containers
413.9 Gas Piping Installations, Discharge of CNG From Motor Vehicle Fuel Storage Containers
The discharge of CNG from motor vehicle fuel cylinders for the purposes of maintenance, cylinder certification, calibration of dispensers or other ...
Fuel Gas Code 2015 of Utah > 4 Gas Piping Installations > 413 (IFGC) Compressed Natural Gas Motor Vehicle Fuel-Dispensing Facilities > 413.9 Discharge of CNG From Motor Vehicle Fuel Storage Containers
413.9.2.3 Gas Piping Installations, Separation
MINIMUM SEPARATION (feet) Buildings 25 Building openings 25 Lot lines 15 Public ways 15 Vehicles 25 CNG compressor and storage ...
Fuel Gas Code 2018 of Utah > 4 Gas Piping Installations > 413 (IFGC) Compressed Natural Gas Motor Vehicle Fuel-Dispensing Facilities > 413.9 Discharge of CNG From Motor Vehicle Fuel Storage Containers > 413.9.2 Atmospheric Venting > 413.9.2.3 Separation
413.9.2.3 Gas Piping Installations, Separation
CNG compressor and storage vessels
25
CNG dispensers
25
For SI: 1 foot = 304.8 mm ...