Luminous directional signs designed in compliance with Section 1025.6.1 shall be placed in the interior exit stairway or ramp at every entrance thereto such that they are readily visible when the doors are in the open and closed positions. Such directional sign shall include an arrow indicating the direction of travel. The word "EXIT" shall not be required. The signs shall be located such that their top edge is within 18 inches (457.2 mm) above the finished floor. Directional signs shall comply with Figure S101.1(9) in Appendix S.