1910.263(l)(11) Direct Recirculating Ovens
JUMP TO FULL CODE CHAPTER
Each circulating fan in direct recirculating ovens shall be interconnected with the burner in such a manner that the fuel is shut off by a safety valve when the fan is not running.
The flame of the burner or burners in direct recirculating ovens shall be protected by a quick-acting flame-sensitive safeguard which will automatically shut off the fuel supply in case of burner failure.
Related Code Sections
1910.263(l)(11) Special Industries, Direct Recirculating Ovens
Each circulating fan in direct recirculating ovens shall be interconnected with the burner in such a manner that the fuel is shut off by a safety ...
OSHA 1910 General Industry > R Special Industries > 1910.263 Bakery Equipment > 1910.263(l) Ovens > 1910.263(l)(11) Direct Recirculating Ovens
1910.263(l)(10) Special Industries, Direct-Fired Ovens
Direct-fired ovens shall be afeguarded against failure of fuel, air, or ignition ...
OSHA 1910 General Industry > R Special Industries > 1910.263 Bakery Equipment > 1910.263(l) Ovens > 1910.263(l)(10) Direct-Fired Ovens
1910.263(l)(15)(i) Special Industries,
[Reserved ...
OSHA 1910 General Industry > R Special Industries > 1910.263 Bakery Equipment > 1910.263(l) Ovens > 1910.263(l)(15) Indirect Recirculating Ovens > 1910.263(l)(15)(i)
1910.263(l)(15)(ii) Special Industries,
[Reserved ...
OSHA 1910 General Industry > R Special Industries > 1910.263 Bakery Equipment > 1910.263(l) Ovens > 1910.263(l)(15) Indirect Recirculating Ovens > 1910.263(l)(15)(ii)
1910.263(l)(15)(iii) Special Industries,
Duct systems (in ovens) operating under pressure shall be tested for tightness in the initial starting of the oven and also at intervals not farther ...
OSHA 1910 General Industry > R Special Industries > 1910.263 Bakery Equipment > 1910.263(l) Ovens > 1910.263(l)(15) Indirect Recirculating Ovens > 1910.263(l)(15)(iii)