10.3.1.1
For columns with a square, octagonal, or other shaped cross section, it shall be permitted to base gross area considered, required reinforcement, and design strength on a circular section with a diameter equal to the least lateral dimension of the actual shape.
10.3.1.2
For columns with cross sections larger than required by considerations of loading, it shall be permitted to base gross area considered, required reinforcement, and design strength on a reduced effective area, not less than one-half the total area. This provision shall not apply to columns in special moment frames or columns not part of the seismic-force-resisting system required to be designed in accordance with Chapter 18.
10.3.1.3
For columns built monolithically with a concrete wall, the outer limits of the effective cross section of the column shall not be taken greater than 1.5 in. outside the transverse reinforcement.
10.3.1.4
For columns with two or more interlocking spirals, outer limits of the effective cross section shall be taken at a distance outside the spirals equal to the minimum required concrete cover.
10.3.1.5
If a reduced effective area is considered according to 10.3.1.1 through 10.3.1.4, structural analysis and design of other parts of the structure that interact with the column shall be based on the actual cross section.

Related Code Sections

10.3.1 Columns, Dimensional Limits
built monolithically with a concrete wall, the outer limits of the effective cross section of the column shall not be taken greater than 1.5 ...
10.3.1 Columns, Dimensional Limits
built monolithically with a concrete wall, the outer limits of the effective cross section of the column shall not be taken greater than 1.5 ...
18.6.2 Earthquake-Resistant Structures, Dimensional Limits
Beams shall satisfy (a) through (c): (a) Clear span ℓn shall be at least 4d (b) Width bw shall be at least the lesser of 0.3h and 10 in. (c ...