1224.4.11.3.1 Dietary and Food Preparation Areas
JUMP TO FULL CODE CHAPTER
Dietary and food preparation areas shall comply with the following requirements:
- In dietary and food preparation areas, wall construction, finish, and trim, including the joints between the walls and the floors, shall be free of spaces that can harbor insects and rodents.
- Wall surfaces in wet areas (e.g., kitchens, environmental services closets) shall be monolithic and all seams shall be covered and/or sealed.
Related Code Sections
1224.4.11.3.1 Interior Environment, Dietary and Food Preparation Areas
Dietary and food preparation areas shall comply with the following requirements: In dietary and food preparation areas, wall construction, finish ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.4 General Construction > 1224.4.11 Interior Finishes > 1224.4.11.3 Wall Finishes > 1224.4.11.3.1 Dietary and Food Preparation Areas
1225.5.2.5.4 Interior Environment, Dietary Area
dietary area in a small house skilled nursing facility shall be designed to accommodate the method of food preparation required. The California ...
Los Angeles Building Code > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.5 Skilled Nursing Unit Models > 1225.5.2 Household Model > 1225.5.2.5 Resident Living Area > 1225.5.2.5.4 Dietary Area
1225.4.2.2.11 Interior Environment, Toilet Rooms
Toilet rooms shall be provided for the exclusive use of the dietary staff. They shall not open directly into the food preparation areas, but shall ...
Los Angeles Building Code > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.4 Common Elements > 1225.4.2 Dietetic Service Space > 1225.4.2.2 Functional Elements > 1225.4.2.2.11 Toilet Rooms
1224.20.2.15 Interior Environment, Toilet Room(s) and Locker Spaces
Toilet rooms shall be provided for the exclusive use of the dietary staff. They shall not open directly into the food preparation areas, but shall ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.20 Dietetic Service Space > 1224.20.2 Functional Elements > 1224.20.2.15 Toilet Room(s) and Locker Spaces
1225.4.2.2 Interior Environment, Functional Elements
Handwashing stations shall be located in the food preparation area ...
Los Angeles Building Code > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.4 Common Elements > 1225.4.2 Dietetic Service Space > 1225.4.2.2 Functional Elements