3.27.3 Device Actuation at Recall Level
Go To Full Code Chapter
If any of the devices specified in 3.27.1(a), 3.27.1(c), or 3.27.1(d) is activated while the car is stationary at the recall level and Phase I Emergency Recall Operation is in effect, the following shall apply:
(a) Automatic power-operated doors shall close within 15 s.
(b) The door open button(s) shall remain operational.
(c) The visual signal (see Figure 2.27.3.1.6) shall illuminate intermittently.