25.4.1 General
25.4.1.1
Calculated tension or compression in reinforcement at each section of a member shall be developed on each side of that section by embedment length; hook, headed deformed bar, mechanical device, or a combination thereof.
25.4.1.2
Hooks and heads shall not be used to develop bars in compression.
25.4.1.3
Development lengths do not require a strength reduction factor ϕ.
25.4.1.4
The values of used to calculate development length shall not exceed 100 psi.
25.4.2 Development of Deformed Bars and Deformed Wires in Tension
25.4.2.1
Development length d for deformed bars and deformed wires in tension shall be the greater of (a) and (b):
(a) Length calculated in accordance with 25.4.2.3 or 25.4.2.4 using the applicable modification factors of 25.4.2.5
(b) 12 in.
25.4.2.2
For bars with fy ≥ 80,000 psi spaced closer than 6 in. on center, transverse reinforcement shall be provided such that Ktr shall not be smaller than 0.5db.
25.4.2.3
For deformed bars or deformed wires, d shall be calculated in accordance with Table 25.4.2.3.
Table 25.4.2.3—Development length for deformed bars and deformed wires in tension
Spacing and cover No. 6 and smaller bars and deformed wires No. 7 and larger bars
Clear spacing of bars or wires being developed or lap spliced not less than db, clear cover at least db, and stirrups or ties throughout d not less than the Code minimum
or
Clear spacing of bars or wires being developed or lap spliced at least 2db and clear cover at least db
Other cases
25.4.2.4
For deformed bars or deformed wires, d shall be calculated by:
(25.4.2.4a)
in which the confinement term (cb + Ktr)/db shall not exceed 2.5, and
(25.4.2.4b)
where n is the number of bars or wires being developed or lap spliced along the plane of splitting. It shall be permitted to use Ktr = 0 as a design simplification even if transverse reinforcement is present or required.
25.4.2.5
For the calculation of d, modification factors shall be in accordance with Table 25.4.2.5.
Table 25.4.2.5—Modification factors for development of deformed bars and deformed wires in tension
Modification factor Condition Value of factor
Lightweight λ Lightweight concrete 0.75
Normalweight concrete 1.0
Reinforcement grade Ψg Grade 40 or Grade 60 1.0
Grade 80 1.15
Grade 100 1.3
Epoxy[1] Ψe Epoxy-coated or zinc and epoxy dual-coated reinforcement with clear cover less than 3db or clear spacing less than 6db 1.5
Epoxy-coated or zinc and epoxy dual-coated reinforcement for all other conditions 1.2
Uncoated or zinc-coated (galvanized) reinforcement 1.0
Size Ψs No. 7 and larger bars 1.0
No. 6 and smaller bars and deformed wires 0.8
Casting position[1] Ψt More than 12 in. of fresh concrete placed below horizontal reinforcement 1.3
Other 1.0
[1]The product ΨtΨe need not exceed 1.7.
25.4.3 Development of Standard Hooks in Tension
25.4.3.1
Development length dh for deformed bars in tension terminating in a standard hook shall be the greater of (a) through (c):
(a) with Ψe, Ψr, Ψo, Ψc, and λ given in 25.4.3.2
(b) 8db
(c) 6 in.
25.4.3.2
For the calculation of dh, modification factors Ψe, Ψr, Ψo, Ψc, and λ shall be in accordance with Table 25.4.3.2. At discontinuous ends of members, 25.4.3.4 shall apply.
Table 25.4.3.2—Modification factors for development of hooked bars in tension
Modification factor Condition Value of factor
Lightweight λ Lightweight concrete 0.75
Normalweight concrete 1.0
Epoxy Ψe Epoxy-coated or zinc and epoxy dual-coated reinforcement 1.2
Uncoated or zinc-coated (galvanized) reinforcement 1.0
Confining reinforcement Ψr For No. 11 and smaller bars with Ath ≥ 0.4Ahs or s[1]6db[2] 1.0
Other 1.6
Location Ψo For No. 11 and smaller diameter hooked bars:
(1) Terminating inside column core with side cover normal to plane of hook ≥ 2.5 in., or
(2) With side cover normal to plane of hook ≥ 6db
1.0
Other 1.25
Concrete strength Ψc For fc' < 6000 psi fc'/15,000 + 0.6
For fc' ≥ 6000 psi 1.0
[1]s is minimum center-to-center spacing of hooked bars.
[2]db is nominal diameter of hooked bar.
25.4.3.3
The total cross-sectional area of ties or stirrups confining hooked bars Ath shall consist of (a) or (b):
  1. Ties or stirrups that enclose the hook and satisfy 25.3.2.
  2. Other reinforcement enclosing the hook, that extends at least 0.75dh from the enclosed hook in the direction of the bar in tension.

    Ath shall be in accordance with (c) or (d). For members with confining reinforcement that is both parallel and perpendicular to dh, it shall be permitted to use the value of Ath based on (c) or (d) that results in the lower value of dh.
  3. Two or more ties or stirrups shall be provided parallel to dh enclosing the hooks, evenly distributed with a center-to-center spacing not exceeding 8db, and within 15db of the centerline of the straight portion of the hooked bars, where db is the nominal diameter of the hooked bar.
  4. Two or more ties or stirrups shall be provided perpendicular to dh, enclosing the hooked bars, and evenly distributed along dh with a center-to-center spacing not exceeding 8db, where db is the nominal diameter of the hooked bar.
25.4.3.4
For bars being developed by a standard hook at discontinuous ends of members with both side cover and top (or bottom) cover to hook less than 2-1/2 in., (a) and (b) shall be satisfied:
(a) The hook shall be enclosed along dh within ties or stirrups perpendicular to dh at s ≤ 3db
(b) The first tie or stirrup shall enclose the bent portion of the hook within 2db of the outside of the bend where db is the nominal diameter of the hooked bar.
25.4.4 Development of Headed Deformed Bars in Tension
25.4.4.1
Use of a head to develop a deformed bar in tension shall be permitted if conditions (a) through (f) are satisfied:
(a) Bar shall conform to 20.2.1.6
(b) Bar size shall not exceed No. 11
(c) Net bearing area of head Abrg shall be at least 4Ab
(d) Concrete shall be normalweight
(e) Clear cover for bar shall be at least 2db
(f) Center-to-center spacing between bars shall be at least 3db
25.4.4.2
Development length dt for headed deformed bars in tension shall be the longest of (a) through (c):
(a) with Ψe, Ψp, Ψo, and Ψc, given in 25.4.4.3
(b) 8db
(c) 6 in.
25.4.4.3
For the calculation of dt, modification factors Ψe, Ψp, Ψo, and Ψc shall be in accordance with Table 25.4.4.3.
Table 25.4.4.3—Modification factors for development of headed bars in tension
Modification factor Condition Value of factor
Epoxy Ψe Epoxy-coated or zinc and epoxy dual-coated reinforcement 1.2
Uncoated or zinc-coated (galvanized) reinforcement 1.0
Parallel tie reinforcement Ψp For No. 11 and smaller bars with Att ≥ 0.3Ahs or s[1]6db[2,3] 1.0
Other 1.6
Location Ψo For headed bars:
(1) Terminating inside column core with side cover to bar ≥ 2.5 in.; or
(2) With side cover to bar ≥ 6db
1.0
Other 1.25
Concrete strength Ψc For fc' < 6000 psi fc'/15,000 + 0.6
For fc' ≥ 6000 psi 1.0
[1]s is minimum center-to-center spacing of headed bars.
[2]db is nominal diameter of headed bar.
[3]Refer to 25.4.4.5.
25.4.4.4
For beam column joints, the total cross-sectional area of parallel tie reinforcement Att shall consist of ties or stirrups oriented parallel to dt and located within 8db of the centerline of the headed bar toward the middle of the joint, where db is the nominal diameter of the headed bar.
25.4.4.5
For anchorages other than in beam-column joints, tie reinforcement, Att, shall not be considered, and Ψp shall be taken as 1.0 provided the spacing is at least 6db.
25.4.4.6
If beam negative moment reinforcement is provided by headed deformed bars that terminate in a joint, the column shall extend above the top of the joint a distance at least the depth h of the joint, where h is the horizontal dimension of the joint in the direction of the forces being considered. Alternatively, the beam reinforcement shall be enclosed by additional vertical joint reinforcement providing equivalent confinement to the top face of the joint.
25.4.5 Development of Mechanically Anchored Deformed Bars in Tension
25.4.5.1
Any mechanical attachment or device capable of developing fy of deformed bars shall be permitted, provided it is approved by the building official in accordance with 1.10. Development of deformed bars shall be permitted to consist of a combination of mechanical anchorage plus additional embedment length of the deformed bars between the critical section and the mechanical attachment or device.
25.4.6 Development of Welded Deformed Wire Reinforcement in Tension
25.4.6.1
Development length d for welded deformed wire reinforcement in tension measured from the critical section to the end of wire shall be the greater of (a) and (b), where wires in the direction of the development length shall all be deformed D31 or smaller.
(a) Length calculated in accordance with 25.4.6.2
(b) 8 in.
25.4.6.2
For welded deformed wire reinforcement, d shall be calculated from 25.4.2.3 or 25.4.2.4, times welded deformed wire reinforcement factor Ψw from 25.4.6.3 or 25.4.6.4. For epoxy-coated welded deformed wire reinforcement meeting 25.4.6.3, it shall be permitted to use Ψe = 1.0 in 25.4.2.3 or 25.4.2.4.
25.4.6.3
For welded deformed wire reinforcement with at least one cross wire within d that is at least 2 in. from the critical section, Ψw shall be the greater of (a) and (b), and need not exceed 1.0:
(a)
(b)
where s is the spacing between the wires to be developed.
25.4.6.4
For welded deformed wire reinforcement with no cross wires within d or with a single cross wire less than 2 in. from the critical section, Ψw shall be taken as 1.0.
25.4.6.5
Where any plain wires, or deformed wires larger than D31, are present in the welded deformed wire reinforcement in the direction of the development length, the reinforcement shall be developed in accordance with 25.4.7.
25.4.6.6
Zinc-coated (galvanized) welded deformed wire reinforcement shall be developed in accordance with 25.4.7.
25.4.7 Development of Welded Plain Wire Reinforcement in Tension
25.4.7.1
Development length d for welded plain wire reinforcement in tension measured from the critical section to the outermost cross wire shall be the greater of (a) and (b) and shall require a minimum of two cross wires within d.
(a) Length calculated in accordance with 25.4.7.2
(b) 6 in.
25.4.7.2
d shall be the greater of (a) and (b):
(a) spacing of cross wires + 2 in.
(b) , where s is the spacing between the wires to be developed, and λ is given in Table 25.4.2.5.
25.4.8 Development of Pretensioned Seven-Wire Strands in Tension
25.4.8.1
Development length d of pretensioned seven-wire strands in tension shall be in accordance with (a) and (b):
(a) (25.4.8.1)
(b) If bonding of a strand does not extend to end of member, and design includes tension at service loads in the precompressed tension zone, d calculated by Eq. (25.4.8.1) shall be doubled.
25.4.8.2
Seven-wire strand shall be bonded at least d beyond the critical section except as provided in 25.4.8.3.
25.4.8.3
Embedment less than d shall be permitted at a section of a member, provided the design strand stress at that section does not exceed values obtained from the bilinear relationship defined by Eq. (25.4.8.1).
25.4.9 Development of Deformed Bars and Deformed Wires in Compression
25.4.9.1
Development length dc for deformed bars and deformed wires in compression shall be the greater of (a) and (b)
(a) Length calculated in accordance with 25.4.9.2
(b) 8 in.
25.4.9.2
dc shall be the greater of (a) and (b), using the modification factors of 25.4.9.3:
(a)
(b) 0.0003fyΨrdb
25.4.9.3
For the calculation of dc, modification factors shall be in accordance with Table 25.4.9.3, except Ψr shall be permitted to be taken as 1.0.
Table 25.4.9.3—Modification factors for deformed bars and wires in compression
Modification factor Condition Value of factor
Lightweight λ Lightweight concrete 0.75
Normalweight concrete 1.0
Confining reinforcement Ψr Reinforcement enclosed within (1), (2), (3), or (4):
(1) a spiral
(2) a circular continuously wound tie with db ≥ 1/4 in. and pitch ≤ 4 in.
(3) No. 4 bar or D20 wire ties in accordance with 25.7.2 spaced ≤ 4 in. on center
(4) hoops in accordance with 25.7.4 spaced ≤ 4 in. on center
0.75
Other 1.0
25.4.10 Reduction of Development Length for Excess Reinforcement
25.4.10.1
Reduction of development lengths defined in 25.4.2.1(a), 25.4.6.1(a), 25.4.7.1(a), and 25.4.9.1(a) shall be permitted by use of the ratio (As,required)/(As,provided), except where prohibited by 25.4.10.2. The modified development lengths shall not be less than the respective minimums specified in 25.4.2.1(b), 25.4.6.1(b), 25.4.7.1(b), and 25.4.9.1(b).
Upcodes Diagrams
See More

Related Code Sections

25.4 Reinforcement Details, Development of Reinforcement
Calculated tension or compression in reinforcement at each section of a member shall be developed on each side of that section by embedment length ...
25.4 Reinforcement Details, Development of Reinforcement
Calculated tension or compression in reinforcement at each section of a member shall be developed on each side of that section by embedment length ...