E202.1 Determining Volume of Piping Systems
JUMP TO FULL CODE CHAPTER
Where required for engineering design purposes, Table E202.1 shall be used to determine the approximate internal volume of water distribution piping.
For SI: 1 ounce = 0.030 liter.
OUNCES OF WATER PER FOOT OF TUBE | |||||||||
---|---|---|---|---|---|---|---|---|---|
Size Nominal, Inch |
Copper Type M |
Copper Type L |
Copper Type K |
CPVC CTS SDR 11 |
CPVC SCH 40 |
CPVC SCH 80 |
PE-RT SDR 9 |
Composite ASTM F1281 |
PEX CTS SDR 9 |
3/8 | 1.06 | 0.97 | 0.84 | NIA | 1.17 | --- | 0.64 | 0.63 | 0.64 |
1/2 | 1.69 | 1.55 | 1.45 | 1.25 | 1.89 | 1.46 | 1.18 | 1.31 | 1.18 |
3/4 | 3.43 | 3.22 | 2.90 | 2.67 | 3.38 | 2.74 | 2.35 | 3.39 | 2.35 |
1 | 5.81 | 5.49 | 5.17 | 4.43 | 5.53 | 4.57 | 3.91 | 5.56 | 3.91 |
11/4 | 8.70 | 8.36 | 8.09 | 6.61 | 9.66 | 8.24 | 5.81 | 8.49 | 5.81 |
11/2 | 12.18 | 11.83 | 11.45 | 9.22 | 13.20 | 11.38 | 8.09 | 13.88 | 8.09 |
2 | 21.08 | 20.58 | 20.04 | 15.79 | 21.88 | 19.11 | 13.86 | 21.48 | 13.86 |
Related Code Sections
E202.1 Sizing of Water Piping System, Determining Volume of Piping Systems
Where required for engineering design purposes, Table E202.1 shall be used to determine the approximate internal volume of water distribution piping ...
2015 Michigan Plumbing Code > E Sizing of Water Piping System > E202 Determination of Pipe Volumes > E202.1 Determining Volume of Piping Systems
A.6.5 Sizing and Capacities of Gas Piping, Example 5: Calculating Pressure Drops Due to Temperature Changes
in the morning the temperature is 40°F (4°C).
If the volume of the piping system is unchanged, then the
formula based ...
2015 Michigan Residential Code > A Sizing and Capacities of Gas Piping > A.6 Examples of Piping System Design and Sizing > A.6.5 Example 5: Calculating Pressure Drops Due to Temperature Changes
1104.4 Refrigeration, Volume Calculations
is located in an air duct system, the volume
of the smallest, enclosed occupied space served by the
duct system shall be used to determine ...
2015 Michigan Mechanical Code > 11 Refrigeration > 1104 System Application Requirements > 1104.4 Volume Calculations
Section M2003 Boilers and Water Heaters, Expansion Tanks
with the volume and
capacity of the system. Tanks shall be capable of withstanding
a hydrostatic test pressure of two and one-half
times the allowable ...
A.6 Sizing and Capacities of Gas Piping, Examples of Piping System Design and Sizing
Determine the
required pipe size of each section and outlet of the piping system
shown in Figure A.6.1, with a designated pressure drop
of 0.5 ...
2015 Michigan Residential Code > A Sizing and Capacities of Gas Piping > A.6 Examples of Piping System Design and Sizing