1613.2.5 Determination of Seismic Design Category
JUMP TO FULL CODE CHAPTER
TABLE 1613.2.5(2)
Structures classified as Risk Category I, II or III that are located where the mapped spectral response acceleration parameter at 1-second period, S1, is greater than or equal to 0.75 shall be assigned to Seismic Design Category E. Structures classified as Risk Category IV that are located where the mapped spectral response acceleration parameter at 1-second period, S1, is greater than or equal to 0.75 shall be assigned to Seismic Design Category F. Other structures shall be assigned to a seismic design category based on their risk category and the design spectral response acceleration parameters, SDS and SD1, determined in accordance with Section 1613.2.4 or the site-specific procedures of ASCE 7. Each building and structure shall be assigned to the more severe seismic design category in accordance with Table 1613.2.5(1) or 1613.2.5(2), irrespective of the fundamental period of vibration of the structure, T.
TABLE 1613.2.5(1)
SEISMIC DESIGN CATEGORY BASED ON SHORT-PERIOD (0.2 second) RESPONSE ACCELERATION
VALUE OF SDS | RISK CATEGORY | ||
I or II | III | IV | |
SDS < 0.167g | A | A | A |
0.167g ≤ SDS < 0.33g | B | B | C |
0.33g ≤ SDS < 0.50g | C | C | D |
0.50g ≤ SDS | D | D | D |
TABLE 1613.2.5(2)
SEISMIC DESIGN CATEGORY BASED ON 1-SECOND PERIOD RESPONSE ACCELERATION
VALUE OF SD1 | RISK CATEGORY | ||
I or II | III | IV | |
SD1 < 0.067g | A | A | A |
0.067g ≤ SD1 < 0.133g | B | B | C |
0.133g ≤ SD1 < 0.20g | C | C | D |
0.20g ≤ SD1 | D | D | D |
Where S1 is less than 0.75, the seismic design category is permitted to be determined from Table 1613.2.5(1) alone where all of the following apply:
- In each of the two orthogonal directions, the approximate fundamental period of the structure, Ta, in each of the two orthogonal directions determined in accordance with Section 12.8.2.1 of ASCE 7, is less than 0.8 Ts determined in accordance with Section 11.8.6 of ASCE 7.
- In each of the two orthogonal directions, the fundamental period of the structure used to calculate the story drift is less than Ts.
- Equation 12.8-2 of ASCE 7 is used to determine the seismic response coefficient, Cs.
- The diaphragms are rigid or are permitted to be idealized as rigid in accordance with Section 12.3.1 of ASCE 7 or, for diaphragms permitted to be idealized as flexible in accordance with Section 12.3.1 of ASCE 7, the distances between vertical elements of the seismic force-resisting system do not exceed 40 feet (12 192 mm).
Where the alternate simplified design procedure of ASCE 7 is used, the seismic design category shall be determined in accordance with ASCE 7.
Related Code Sections
1613.2.5 Structural Design, Determination of Seismic Design Category
procedure of ASCE 7 is used, the seismic design category shall be determined in accordance with ASCE 7 ...
Building Code 2018 of Illinois > 16 Structural Design > 1613 Earthquake Loads > 1613.2 Seismic Ground Motion Values > 1613.2.5 Determination of Seismic Design Category
1613.2.5 Structural Design, Determination of Seismic Design Category
Where S1 is less than 0.75, the seismic design category is permitted to be determined from Table 1613.2.5(1) alone where all ...
Building Code 2021 of Illinois > 16 Structural Design > 1613 Earthquake Loads > 1613.2 Seismic Ground Motion Values > 1613.2.5 Determination of Seismic Design Category
1613.3 Structural Design, Ballasted Photovoltaic Panel Systems
determined by acceptable engineering principles. In structures assigned to Seismic Design Category C, D, E or F, ballasted nonpenetrating systems ...
Building Code 2018 of Illinois > 16 Structural Design > 1613 Earthquake Loads > 1613.3 Ballasted Photovoltaic Panel Systems
1613.3 Structural Design, Ballasted Photovoltaic Panel Systems
determined by acceptable engineering principles. In structures assigned to Seismic Design Category C, D, E or F, ballasted nonpenetrating systems ...
Building Code 2021 of Illinois > 16 Structural Design > 1613 Earthquake Loads > 1613.3 Ballasted Photovoltaic Panel Systems
1613.2 Structural Design, Seismic Ground Motion Values
) (Equation 16-37) but SMS shall not be taken less than SM1 except when determining the seismic design category in accordance with Section 1613.2.5 ...
Building Code 2018 of Illinois > 16 Structural Design > 1613 Earthquake Loads > 1613.2 Seismic Ground Motion Values