The minimum length of full-height sheathing on each braced wall line shall be determined by multiplying the length of the braced wall line by the percentage obtained from Table R603.9.2(1) and by the plan aspect-ratio adjustment factors obtained from Table R603.9.2(2). The minimum length of full-height sheathing shall be not less than 20 percent of the braced wall line length.
To be considered full-height sheathing, structural sheathing shall extend from the bottom to the top of the wall without interruption by openings. Only sheathed, full-height wall sections, uninterrupted by openings, which are not less than 48 inches (1219 mm) wide, shall be counted toward meeting the minimum percentages in Table R603.9.2(1). In addition, structural sheathing shall comply with all of the following requirements:
  1. Be installed with the long dimension parallel to the stud framing and shall cover the full vertical height of wall from the bottom of the bottom track to the top of the top track of each story. Installing the long dimension perpendicular to the stud framing or using shorter segments shall be permitted provided that the horizontal joint is blocked as described in Item 2.
  2. Be blocked where the long dimension is installed perpendicular to the stud framing. Blocking shall be not less than 33 mil (0.84 mm) thickness. Each horizontal structural sheathing panel shall be fastened with No. 8 screws spaced at 6 inches (152 mm) on center to the blocking at the joint.
  3. Be applied to each end (corners) of each of the exterior walls with a minimum 48-inch-wide (1219 mm) panel.
Exception: Where stone or masonry veneer is installed, the required length of full-height sheathing and overturning anchorage required shall be determined in accordance with Section R603.9.5.

MINIMUM PERCENTAGE OF FULL-HEIGHT STRUCTURAL SHEATHING ON EXTERIOR WALLSa, b
WALL SUPPORTING ROOF SLOPE ULTIMATE WIND SPEED AND EXPOSURE (mph)
115 B 120 B 130 B < 140 B < 130 C < 140 C
115 C 120 C
Roof and ceiling only
(one story or top floor of two- or three-story building)
3:12 9 11 11 13 17 20
6:12 13 15 17 22 28 35
9:12 23 27 29 33 53 59
12:12 32 39 40 44 70 76
One story, roof and ceiling
(first floor of a two-story building or second floor of a three-story building)
3:12 26 32 34 39 53 67
6:12 27 33 34 44 61 75
9:12 38 45 46 61 78 92
12:12 43 53 57 72 106 116
Two stories, roof and ceiling
(first floor of a three-story building)
3:12 43 53 57 64 89 113
6:12 41 51 51 67 95 114
9:12 53 63 63 89 104 126
12:12 54 67 74 100 142 157
For SI: 1 mph = 0.447 m/s.
  1. Linear interpolation is permitted.
  2. For hip-roofed homes the minimum percentage of full-height sheathing, based on wind, is permitted to be multiplied by a factor of 0.95 for roof slopes not exceeding 7:12 and a factor of 0.9 for roof slopes greater than 7:12.
FULL-HEIGHT SHEATHING LENGTH ADJUSTMENT FACTORS
PLAN ASPECT RATIO LENGTH ADJUSTMENT FACTORS
Short wall Long wall
1:1 1.0 1.0
1.5:1 1.5 0.67
2:1 2.0 0.50
3:1 3.0 0.33
4:1 4.0 0.25
R603.9.2.1 Full-Height Sheathing
The minimum percentage of full-height structural sheathing shall be multiplied by 1.10 for 9-foot-high (2743 mm) walls and multiplied by 1.20 for 10-foot-high (3048 mm) walls.
R603.9.2.2 Full-Height Sheathing in Lowest Story
In the lowest story of a dwelling, multiplying the percentage of full-height sheathing required in Table R603.9.2(1) by 0.6 shall be permitted where hold-down anchors are provided in accordance with Section R603.9.4.2.
Upcodes Diagrams

Related Code Sections

R602.12.3.1 Wall Construction, Multiple Bracing Units
number of bracing units shall be determined by dividing the wall segment length by the minimum bracing unit length. Full-height sheathed segments ...