// CODE SNIPPET
22.4.4.9 Detection, Alarm, and Communications Systems (Nonsprinklered Buildings)
Go To Full Code Chapter
22.4.4.9.1 Initiation
Initiation of the fire alarm system required by 22.3.4.1 shall be by manual means in accordance with 9.6.2 and by means of any required detection devices or detection systems, unless otherwise permitted by the following:
- Manual fire alarm boxes shall be permitted to be locked, provided that staff is present within the area when it is occupied and staff has keys readily available to unlock the boxes.
- Manual fire alarm boxes shall be permitted to be located in a staff location, provided that both of the following criteria are met:
22.4.4.9.2 Detection
An approved automatic smoke detection system shall be in accordance with Section 9.6, as modified by 22.4.4.9.2.1 and 22.4.4.9.2.2, throughout all resident sleeping areas and adjacent day rooms, activity rooms, or contiguous common spaces.
22.4.4.9.2.1
Smoke detectors shall not be required in sleeping rooms with four or fewer occupants in Use Condition II or Use Condition III.
22.4.4.9.2.2
Other arrangements and positioning of smoke detectors shall be permitted to prevent damage or tampering, or for other purposes. Such arrangements shall be capable of detecting any fire, and the placement of detectors shall be such that the speed of detection is equivalent to that provided by the spacing and arrangements required by the installation standards referenced in Section 9.6. Detectors shall be permitted to be located in exhaust ducts from cells, behind grilles, or in other locations. The equivalent performance of the design, however, shall be acceptable to the authority having jurisdiction in accordance with the equivalency concepts specified in Section 1.4.
Related Code Sections
22.4.4.9 New Detention and Correctional Occupancies, Detection, Alarm, and Communications Systems (Nonsprinklered Buildings)
Initiation of the fire alarm system required by 22.3.4.1 shall be by manual means in accordance with 9.6.2 and by means of any required detection ...
Section 3805 Higher Education Laboratories, Nonsprinklered Laboratories
fire detection system shall be installed in all existing laboratories in nonsprinklered buildings in accordance with this section. Detectors shall ...
28.3.4.5 New Hotels and Dormitories, Detection
A corridor smoke detection system in accordance with Section 9.6 shall be provided in buildings other than those protected throughout by an approved ...
31.3.4.4 Existing Apartment Buildings, Detection
In buildings using Option 2, a complete automatic fire detection system in accordance with 9.6.1.3 and 31.3.4.4.2 shall be required ...