// CODE SNIPPET
516.2 Design Restrictions
JUMP TO FULL CODE CHAPTER
Recirculating systems shall comply with Section 516.2.1 through Section 516.2.9. [NFPA 96:13.2]
Gas-fueled or electrically fueled cooking appliances shall be used. Listed gas-fueled equipment designed for use with specific recirculating systems shall have the flue outlets connected in the intended manner. Gas-fueled appliances shall have not less than 18 inches (457 mm) of clearance from the flue outlet to the filter inlet in accordance with Section 509.2.2 through Section 509.2.2.3 and shall be in accordance with the installation requirements of NFPA 54 or NFPA 58. [NFPA 96:13.2.1 — 13.2.3]
Recirculating systems shall be listed with a testing laboratory in accordance with UL 710B or equivalent. [NFPA 96:13.2.4]
Cooking appliances that require protection and that are under a recirculating hood shall be protected by either the integral fire protection system in accordance with UL 710B or Section 513.0. [NFPA 96:13.2.4.2]
A recirculating system shall not use cooking equipment that exceeds that recirculating system's labeled maximum limits for that type of equipment, stated in maximum energy input, maximum cooking temperature, and maximum square area of cooking surface or cubic volume of cooking cavity. [NFPA 96:13.2.6]
The listing label shall show the type(s) of cooking equipment tested and the maximum limits specified in Section 516.2.4. [NFPA 96:13.2.7]
A fire-actuated damper shall be installed at the exhaust outlet of the system. [NFPA 96:13.2.8] The actuation device for the fire damper shall have a maximum temperature rating of 375°F (191°C). [NFPA 96:13.2.10]
The power supply of an electrostatic precipitator (ESP) shall be of the "cold spark," ferroresonant type in which the voltage falls off as the current draw of a short increases. [NFPA 96:13.2.11]
Listing evaluation shall include the following:
- Capture and containment of vapors at published and labeled airflows.
- Grease discharge at the exhaust outlet of the system not to exceed an average of 2.9 E-09 (oz/in3) (5.0 E- 06 kg/m3) of exhausted air sampled from that equipment at maximum amount of product that is capable of being processed over a continuous 8 hour test with the system operating at its minimum listed airflow.
- Listing and labeling of clearance to combustibles from the sides, top, and bottom.
- Electrical connection in the field in accordance with NFPA 70.
- Interlocks on removable components that lie in the path of airflow within the unit to ensure that they are in place during operation of the cooking appliance. [NFPA 96:13.2.12]
Related Code Sections
516.2 Exhaust Systems, Design Restrictions
] Gas-fueled or electrically fueled cooking appliances shall be used. Listed gas-fueled equipment designed ...
Uniform Mechanical Code 2018 of Nevada > 5 Exhaust Systems > 516.0 Recirculating Systems > 516.2 Design Restrictions
516.2.6 Exhaust Systems, Fire Damper
A fire-actuated damper shall be installed at the exhaust outlet of the system. [NFPA 96:13.2.8] The actuation device for the fire damper shall have ...
Uniform Mechanical Code 2018 of Nevada > 5 Exhaust Systems > 516.0 Recirculating Systems > 516.2 Design Restrictions > 516.2.6 Fire Damper
516.2.7 Exhaust Systems, Installation of Electrical Wiring
No electrical wiring shall be installed in the interior sections of the hood plenum that is capable of becoming exposed to grease. Exception: As ...
Uniform Mechanical Code 2018 of Nevada > 5 Exhaust Systems > 516.0 Recirculating Systems > 516.2 Design Restrictions > 516.2.7 Installation of Electrical Wiring
516.2.8 Exhaust Systems, Power Supply
The power supply of an electrostatic precipitator (ESP) shall be of the "cold spark," ferroresonant type in which the voltage falls off as the current ...
Uniform Mechanical Code 2018 of Nevada > 5 Exhaust Systems > 516.0 Recirculating Systems > 516.2 Design Restrictions > 516.2.8 Power Supply
516.2.9 Exhaust Systems, Listing Evaluation
Listing evaluation shall include the following: Capture and containment of vapors at published and labeled airflows. Grease discharge ...
Uniform Mechanical Code 2018 of Nevada > 5 Exhaust Systems > 516.0 Recirculating Systems > 516.2 Design Restrictions > 516.2.9 Listing Evaluation