R404.1.2 Design of Masonry Foundation Walls
JUMP TO FULL CODE CHAPTER
Masonry foundation walls shall be designed and constructed in accordance with the provisions of this section or in accordance with the provisions of TMS 402/ACI 530/ASCE 5. When TMS 402/ACI 530/ASCE 5 or the provisions of this section are used to design masonry foundation walls, project drawings, typical details and specifications are not required to bear the seal of the architect or engineer responsible for design, unless otherwise required by the state law of the jurisdiction having authority.
MAXIMUM UNSUPPORTED HEIGHT OF BASEMENT WALL (feet) |
LOCATION OF HORIZONTAL REINFORCEMENT |
≤ 8 | One No. 4 bar within 12 inches of the top of the wall story and one No. 4 bar near mid-height of the wall story. |
> 8 | One No. 4 bar within 12 inches of the top of the wall story and one No. 4 bar near third points in the wall story. |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa.
MAXIMUM UNSUPPORTED WALL HEIGHT (feet) |
MAXIMUM UNBALANCED BACKFILL HEIGHTf (feet) |
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches) | ||
Soil classesa and design lateral soil (psf per foot of depth) | ||||
GW, GP, SW, SP 30 |
GM, GC, SM, SM-SC and ML 45 |
SC, ML-CL and inorganic CL 60 |
||
8 | 4 | NR | NR | NR |
5 | NR | 6 @ 39 | 6 @ 48 | |
6 | 5 @ 39 | 6 @ 48 | 6 @ 35 | |
7 | 6 @ 48 | 6 @ 34 | 6 @ 25 | |
8 | 6 @ 39 | 6 @ 25 | 6 @ 18 | |
9 | 4 | NR | NR | NR |
5 | NR | 5 @ 37 | 6 @ 48 | |
6 | 5 @ 36 | 6 @ 44 | 6 @ 32 | |
7 | 6 @ 47 | 6 @ 30 | 6 @ 22 | |
8 | 6 @ 34 | 6 @ 22 | 6 @ 16 | |
9 | 6 @ 27 | 6 @ 17 | DR | |
10 | 4 | NR | NR | NR |
5 | NR | 5 @ 35 | 6 @ 48 | |
6 | 6 @ 48 | 6 @ 41 | 6 @ 30 | |
7 | 6 @ 43 | 6 @ 28 | 6 @ 20 | |
8 | 6 @ 31 | 6 @ 20 | DR | |
9 | 6 @ 24 | 6 @ 15 | DR | |
10 | 6 @ 19 | DR | DR |
For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.
NR = Not required.
NR = Not required.
- Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
- Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
- Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
- Deflection criterion isL/240, where L is the height of the basement wall in inches.
- Interpolation is not permitted.
- Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
- NR indicates no vertical wall reinforcement is required, except for 6-inch-nominal walls formed with stay-in-place forming systems in which case vertical reinforcement shall be No. 4@48 inches on center.
- See Section R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
- See Table R608.3 for tolerance from nominal thickness permitted for flat walls.
- DR means design is required in accordance with the applicable building code, or where there is no code, in accordance with ACI 318.
- The use of this table shall be prohibited for soil classifications not shown.
MAXIMUM UNSUPPORTED WALL HEIGHT (feet) |
MAXIMUM UNBALANCED BACKFILL HEIGHTg (feet) |
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches) | ||
Soil classesa and design lateral soil (psf per foot of depth) | ||||
GW, GP, SW, SP 30 |
GM, GC, SM, SM-SC and ML 45 |
SC, ML-CL and inorganic CL 60 |
||
8 | 4 | NR | NR | NR |
5 | NR | NR | NR | |
6 | NR | NR | 6 @ 37 | |
7 | NR | 6 @ 36 | 6 @ 35 | |
8 | 6 @ 41 | 6 @ 35 | 6 @ 26 | |
9 | 4 | NR | NR | NR |
5 | NR | NR | NR | |
6 | NR | NR | 6 @ 35 | |
7 | NR | 6 @ 35 | 6 @ 32 | |
8 | 6 @ 36 | 6 @ 32 | 6 @ 23 | |
9 | 6 @ 35 | 6 @ 25 | 6 @ 18 | |
10 | 4 | NR | NR | NR |
5 | NR | NR | NR | |
6 | NR | NR | 6 @ 35 | |
7 | NR | 6 @ 35 | 6 @ 29 | |
8 | 6 @ 35 | 6 @ 29 | 6 @ 21 | |
9 | 6 @ 34 | 6 @ 22 | 6 @ 16 | |
10 | 6 @ 27 | 6 @ 17 | 6 @ 13 |
For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.
NR = Not required.
NR = Not required.
- Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
- Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi, concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
- Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
- NR indicates no vertical reinforcement is required.
- Deflection criterion is L/240, where L is the height of the basement wall in inches.
- Interpolation is not permitted.
- Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
- See Section R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
- See Table R608.3 for tolerance from nominal thickness permitted for flat walls.
- The use of this table shall be prohibited for soil classifications not shown.
MAXIMUM UNSUPPORTED WALL HEIGHT (feet) |
MAXIMUM UNBALANCED BACKFILL HEIGHTg (feet) |
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches) | ||
Soil classesa and design lateral soil (psf per foot of depth) | ||||
GW, GP, SW, SP 30 |
GM, GC, SM, SM-SC and ML 45 |
SC, ML-CL and inorganic CL 60 |
||
8 | 4 | NR | NR | NR |
5 | NR | NR | NR | |
6 | NR | NR | NR | |
7 | NR | NR | NR | |
8 | 6 @ 48 | 6 @ 35 | 6 @ 28 | |
9 | 4 | NR | NR | NR |
5 | NR | NR | NR | |
6 | NR | NR | NR | |
7 | NR | NR | 6 @ 31 | |
8 | NR | 6 @ 31 | 6 @ 28 | |
9 | 6 @ 37 | 6 @ 28 | 6 @ 24 | |
10 | 4 | NR | NR | NR |
5 | NR | NR | NR | |
6 | NR | NR | NR | |
7 | NR | NR | 6 @ 28 | |
8 | NR | 6 @ 28 | 6 @ 28 | |
9 | 6 @ 33 | 6 @ 28 | 6 @ 21 | |
10 | 6 @ 28 | 6 @ 23 | 6 @ 17 |
For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.
NR = Not required.
NR = Not required.
- Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
- Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
- Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
- NR indicates no vertical reinforcement is required.
- Deflection criterion is L/240, where L is the height of the basement wall in inches.
- Interpolation is not permitted.
- Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
- See Section R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
- See Table R608.3 for tolerance from nominal thickness permitted for flat walls.
- The use of this table shall be prohibited for soil classifications not shown.
MAXIMUM UNSUPPORTED WALL HEIGHT (feet) |
MAXIMUM UNBALANCED BACKFILL HEIGHTf (feet) |
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches) | ||
Soil classesa and design lateral soil (psf per foot of depth) | ||||
GW, GP, SW, SP 30 |
GM, GC, SM, SM-SC and ML 45 |
SC, ML-CL and inorganic CL 60 |
||
8 | 4 | 4 @ 48 | 4 @ 46 | 6 @ 39 |
5 | 4 @ 45 | 5 @ 46 | 6 @ 47 | |
6 | 5 @ 45 | 6 @ 40 | DR | |
7 | 6 @ 44 | DR | DR | |
8 | 6 @ 32 | DR | DR | |
9 | 4 | 4 @ 48 | 4 @ 46 | 4 @ 37 |
5 | 4 @ 42 | 5 @ 43 | 6 @ 44 | |
6 | 5 @ 41 | 6 @ 37 | DR | |
7 | 6 @ 39 | DR | DR | |
> 8 | DRi | DR | DR | |
10 | 4 | 4 @ 48 | 4 @ 46 | 4 @ 35 |
5 | 4 @ 40 | 5 @ 40 | 6 @ 41 | |
6 | 5 @ 38 | 6 @ 34 | DR | |
7 | 6 @ 36 | DR | DR | |
> 8 | DR | DR | DR |
For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.
- Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
- Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
- Maximum spacings shown are the values calculated for the specified bar size. Where the bar used is Grade 60 and the size specified in the table, the actual spacing in the wall shall not exceed a whole-number multiple of 12 inches (i.e., 12, 24, 36 and 48) that is less than or equal to the tabulated spacing. Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
- Deflection criterion is L/240, where L is the height of the basement wall in inches.
- Interpolation is not permitted.
- Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
- See Section R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
- See Table R608.3 for thicknesses and dimensions of waffle-grid walls.
- DR means design is required in accordance with the applicable building code, or where there is no code, in accordance with ACI 318.
- The use of this table shall be prohibited for soil classifications not shown.
MAXIMUM UNSUPPORTED WALL HEIGHT (feet) |
MAXIMUM UNBALANCED BACKFILL HEIGHTg (feet) |
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches) | ||
Soil classesa and design lateral soil (psf per foot of depth) | ||||
GW, GP, SW, SP 30 |
GM, GC, SM, SM-SC and ML 45 |
SC, ML-CL and inorganic CL 60 |
||
8 | 4 | NR | NR | NR |
5 | NR | 5 @ 48 | 5 @ 46 | |
6 | 5 @ 48 | 5 @ 43 | 6 @ 45 | |
7 | 5 @ 46 | 6 @ 43 | 6 @ 31 | |
8 | 6 @ 48 | 6 @ 32 | 6 @ 23 | |
9 | 4 | NR | NR | NR |
5 | NR | 5 @ 47 | 5 @ 46 | |
6 | 5 @ 46 | 5 @ 39 | 6 @ 41 | |
7 | 5 @ 42 | 6 @ 38 | 6 @ 28 | |
8 | 6 @ 44 | 6 @ 28 | 6 @ 20 | |
9 | 6 @ 34 | 6 @ 21 | DR | |
10 | 4 | NR | NR | NR |
5 | NR | 5 @ 46 | 5 @ 44 | |
6 | 5 @ 46 | 5 @ 37 | 6 @ 38 | |
7 | 5 @ 38 | 6 @ 35 | 6 @ 25 | |
8 | 6 @ 39 | 6 @ 25 | DR | |
9 | 6 @ 30 | DR | DR | |
10 | 6 @ 24 | DR | DR |
For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.
NR = Not required.
NR = Not required.
- Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
- Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
- Maximum spacings shown are the values calculated for the specified bar size. Where the bar used is Grade 60 (420 MPa) and the size specified in the table, the actual spacing in the wall shall not exceed a whole-number multiple of 12 inches (i.e., 12, 24, 36 and 48) that is less than or equal to the tabulated spacing. Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
- NR indicates no vertical reinforcement is required.
- Deflection criterion is L/240, where L is the height of the basement wall in inches.
- Interpolation shall not be permitted.
- Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
- See Section R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
- See Table R608.3 for thicknesses and dimensions of waffle-grid walls.
- DR means design is required in accordance with the applicable building code, or where there is no code, in accordance with ACI 318.
- The use of this table shall be prohibited for soil classifications not shown.
MAXIMUM UNSUPPORTED WALL HEIGHT (feet) |
MAXIMUM UNBALANCED BACKFILL HEIGHTf (feet) |
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches) | ||
Soil classesa and design lateral soil (psf per foot of depth) | ||||
GW, GP, SW, SP 30 |
GM, GC, SM, SM-SC and ML 45 |
SC, ML-CL and inorganic CL 60 |
||
8 | 4 | 4 @ 48 | 4 @ 48 | 5 @ 43 |
5 | 4 @ 48 | 5 @ 48 | 5 @ 37 | |
6 | 5 @ 48 | 6 @ 45 | 6 @ 32 | |
7 | 6 @ 48 | DR | DR | |
8 | 6 @ 36 | DR | DR | |
9 | 4 | 4 @ 48 | 4 @ 48 | 4 @ 41 |
5 | 4 @ 48 | 5 @ 48 | 6 @ 48 | |
6 | 5 @ 45 | 6 @ 41 | DR | |
7 | 6 @ 43 | DR | DR | |
> 8 | DR | DR | DR | |
10 | 4 | 4 @ 48 | 4 @ 48 | 4 @ 39 |
5 | 4 @ 44 | 5 @ 44 | 6 @ 46 | |
6 | 5 @ 42 | 6 @ 38 | DR | |
7 | 6 @ 40 | DR | DR | |
> 8 | DR | DR | DR |
For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.
- Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
- Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi, concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
- Maximum spacings shown are the values calculated for the specified bar size. Where the bar used is Grade 60 and the size specified in the table, the actual spacing in the wall shall not exceed a whole-number multiple of 12 inches (i.e., 12, 24, 36 and 48) that is less than or equal to the tabulated spacing. Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
- Deflection criterion is L/240, where L is the height of the basement wall in inches.
- Interpolation is not permitted.
- Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
- See Sections R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
- See Table R608.3 for thicknesses and dimensions of screen-grid walls.
- DR means design is required in accordance with the applicable building code, or where there is no code, in accordance with ACI 318.
- The use of this table shall be prohibited for soil classifications not shown.
MAXIMUM WALL HEIGHT (feet) |
MAXIMUM UNBALANCED BACKFILL HEIGHTg (feet) |
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches) | |||||||||||
Soil classesa and design lateral soil (psf per foot of depth) | |||||||||||||
GW, GP, SW, SP 30 |
GM, GC, SM, SM-SC and ML 45 |
SC, ML-CL and inorganic CL 60 |
|||||||||||
Minimum nominal wall thickness (inches) | |||||||||||||
6 | 8 | 10 | 12 | 6 | 8 | 10 | 12 | 6 | 8 | 10 | 12 | ||
5 | 4 | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
5 | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | |
6 | 4 | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
5 | NR | NR | NR | NR | NR | NRl | NR | NR | 4 @ 35 | NRl | NR | NR | |
6 | NR | NR | NR | NR | 5 @ 48 | NR | NR | NR | 5 @ 36 | NR | NR | NR | |
7 | 4 | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
5 | NR | NR | NR | NR | NR | NR | NR | NR | 5 @ 47 | NR | NR | NR | |
6 | NR | NR | NR | NR | 5 @ 42 | NR | NR | NR | 6 @ 43 | 5 @ 48 | NRl | NR | |
7 | 5 @ 46 | NR | NR | NR | 6 @ 42 | 5 @ 46 | NRl | NR | 6 @ 34 | 6 @ 48 | NR | NR | |
8 | 4 | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
5 | NR | NR | NR | NR | 4 @ 38 | NRl | NR | NR | 5 @ 43 | NR | NR | NR | |
6 | 4 @ 37 | NRl | NR | NR | 5 @ 37 | NR | NR | NR | 6 @ 37 | 5 @ 43 | NRl | NR | |
7 | 5 @ 40 | NR | NR | NR | 6 @ 37 | 5 @ 41 | NRl | NR | 6 @ 34 | 6 @ 43 | NR | NR | |
8 | 6 @ 43 | 5 @ 47 | NRl | NR | 6 @ 34 | 6 @ 43 | NR | NR | 6 @ 27 | 6 @ 32 | 6 @ 44 | NR | |
9 | 4 | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
5 | NR | NR | NR | NR | 4 @ 35 | NRl | NR | NR | 5 @ 40 | NR | NR | NR | |
6 | 4 @ 34 | NRl | NR | NR | 6 @ 48 | NR | NR | NR | 6 @ 36 | 6 @ 39 | NRl | NR | |
7 | 5 @ 36 | NR | NR | NR | 6 @ 34 | 5 @ 37 | NR | NR | 6 @ 33 | 6 @ 38 | 5 @ 37 | NRl | |
8 | 6 @ 38 | 5 @ 41 | NRl | NR | 6 @ 33 | 6 @ 38 | 5 @ 37 | NRl | 6 @ 24 | 6 @ 29 | 6 @ 39 | 4 @ 48m | |
9 | 6 @ 34 | 6 @ 46 | NR | NR | 6 @ 26 | 6 @ 30 | 6 @ 41 | NR | 6 @ 19 | 6 @ 23 | 6 @ 30 | 6 @ 39 | |
10 | 4 | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
5 | NR | NR | NR | NR | 4 @ 33 | NRl | NR | NR | 5 @ 38 | NR | NR | NR | |
6 | 5 @ 48 | NRl | NR | NR | 6 @ 45 | NR | NR | NR | 6 @ 34 | 5 @ 37 | NR | NR | |
7 | 6 @ 47 | NR | NR | NR | 6 @ 34 | 6 @ 48 | NR | NR | 6 @ 30 | 6 @ 35 | 6 @ 48 | NRl | |
8 | 6 @ 34 | 5 @ 38 | NR | NR | 6 @ 30 | 6 @ 34 | 6 @ 47 | NRl | 6 @ 22 | 6 @ 26 | 6 @ 35 | 6 @ 45m | |
9 | 6 @ 34 | 6 @ 41 | 4 @ 48 | NRl | 6 @ 23 | 6 @ 27 | 6 @ 35 | 4 @ 48m | DR | 6 @ 22 | 6 @ 27 | 6 @ 34 | |
10 | 6 @ 28 | 6 @ 33 | 6 @ 45 | NR | DRj | 6 @ 23 | 6 @ 29 | 6 @ 38 | DR | 6 @ 22 | 6 @ 22 | 6 @ 28 |
For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.
NR = Not required.
NR = Not required.
- Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
- Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi.
- Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
- NR indicates no vertical wall reinforcement is required, except for 6-inch nominal walls formed with stay-in-place forming systems in which case vertical reinforcement shall be No. 4@48 inches on center.
- Allowable deflection criterion is L/240, where L is the unsupported height of the basement wall in inches.
- Interpolation is not permitted.
- Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
- Vertical reinforcement shall be located to provide a cover of 11/4 inches measured from the inside face of the wall. The center of the steel shall not vary from the specified location by more than the greater of 10 percent of the wall thickness or 3/8 inch.
- Concrete cover for reinforcement measured from the inside face of the wall shall be not less than 3/4 inch. Concrete cover for reinforcement measured from the outside face of the wall shall be not less than 11/2 inches for No. 5 bars and smaller, and not less than 2 inches for larger bars.
- DR means design is required in accordance with the applicable building code, or where there is no code, in accordance with ACI 318.
- Concrete shall have a specified compressive strength, f 'c, of not less than 2,500 psi at 28 days, unless a higher strength is required by Footnote l or m.
- The minimum thickness is permitted to be reduced 2 inches, provided the minimum specified compressive strength of concrete, f ' c, is 4,000 psi.
- A plain concrete wall with a minimum nominal thickness of 12 inches is permitted, provided minimum specified compressive strength of concrete, f 'c, is 3,500 psi.
- See Table R608.3 for tolerance from nominal thickness permitted for flat walls.
- The use of this table shall be prohibited for soil classifications not shown.
BAR SPACING FROM APPLICABLE TABLE IN SECTION R404.1.3.2 (inches) |
BAR SIZE FROM APPLICABLE TABLE IN SECTION R404.1.3.2 | ||||||||||||||
#4 | #5 | #6 | |||||||||||||
Alternate bar size and/or alternate grade of steel desired | |||||||||||||||
Grade 60 | Grade 40 | Grade 60 | Grade 40 | Grade 60 | Grade 40 | ||||||||||
#5 | #6 | #4 | #5 | #6 | #4 | #6 | #4 | #5 | #6 | #4 | #5 | #4 | #5 | #6 | |
Maximum spacing for alternate bar size and/or alternate grade of steel (inches) | |||||||||||||||
8 | 12 | 18 | 5 | 8 | 12 | 5 | 11 | 3 | 5 | 8 | 4 | 6 | 2 | 4 | 5 |
9 | 14 | 20 | 6 | 9 | 13 | 6 | 13 | 4 | 6 | 9 | 4 | 6 | 3 | 4 | 6 |
10 | 16 | 22 | 7 | 10 | 15 | 6 | 14 | 4 | 7 | 9 | 5 | 7 | 3 | 5 | 7 |
11 | 17 | 24 | 7 | 11 | 16 | 7 | 16 | 5 | 7 | 10 | 5 | 8 | 3 | 5 | 7 |
12 | 19 | 26 | 8 | 12 | 18 | 8 | 17 | 5 | 8 | 11 | 5 | 8 | 4 | 6 | 8 |
13 | 20 | 29 | 9 | 13 | 19 | 8 | 18 | 6 | 9 | 12 | 6 | 9 | 4 | 6 | 9 |
14 | 22 | 31 | 9 | 14 | 21 | 9 | 20 | 6 | 9 | 13 | 6 | 10 | 4 | 7 | 9 |
15 | 23 | 33 | 10 | 16 | 22 | 10 | 21 | 6 | 10 | 14 | 7 | 11 | 5 | 7 | 10 |
16 | 25 | 35 | 11 | 17 | 23 | 10 | 23 | 7 | 11 | 15 | 7 | 11 | 5 | 8 | 11 |
17 | 26 | 37 | 11 | 18 | 25 | 11 | 24 | 7 | 11 | 16 | 8 | 12 | 5 | 8 | 11 |
18 | 28 | 40 | 12 | 19 | 26 | 12 | 26 | 8 | 12 | 17 | 8 | 13 | 5 | 8 | 12 |
19 | 29 | 42 | 13 | 20 | 28 | 12 | 27 | 8 | 13 | 18 | 9 | 13 | 6 | 9 | 13 |
20 | 31 | 44 | 13 | 21 | 29 | 13 | 28 | 9 | 13 | 19 | 9 | 14 | 6 | 9 | 13 |
21 | 33 | 46 | 14 | 22 | 31 | 14 | 30 | 9 | 14 | 20 | 10 | 15 | 6 | 10 | 14 |
22 | 34 | 48 | 15 | 23 | 32 | 14 | 31 | 9 | 15 | 21 | 10 | 16 | 7 | 10 | 15 |
23 | 36 | 48 | 15 | 24 | 34 | 15 | 33 | 10 | 15 | 22 | 10 | 16 | 7 | 11 | 15 |
24 | 37 | 48 | 16 | 25 | 35 | 15 | 34 | 10 | 16 | 23 | 11 | 17 | 7 | 11 | 16 |
25 | 39 | 48 | 17 | 26 | 37 | 16 | 35 | 11 | 17 | 24 | 11 | 18 | 8 | 12 | 17 |
26 | 40 | 48 | 17 | 27 | 38 | 17 | 37 | 11 | 17 | 25 | 12 | 18 | 8 | 12 | 17 |
27 | 42 | 48 | 18 | 28 | 40 | 17 | 38 | 12 | 18 | 26 | 12 | 19 | 8 | 13 | 18 |
28 | 43 | 48 | 19 | 29 | 41 | 18 | 40 | 12 | 19 | 26 | 13 | 20 | 8 | 13 | 19 |
29 | 45 | 48 | 19 | 30 | 43 | 19 | 41 | 12 | 19 | 27 | 13 | 20 | 9 | 14 | 19 |
30 | 47 | 48 | 20 | 31 | 44 | 19 | 43 | 13 | 20 | 28 | 14 | 21 | 9 | 14 | 20 |
31 | 48 | 48 | 21 | 32 | 45 | 20 | 44 | 13 | 21 | 29 | 14 | 22 | 9 | 15 | 21 |
32 | 48 | 48 | 21 | 33 | 47 | 21 | 45 | 14 | 21 | 30 | 15 | 23 | 10 | 15 | 21 |
33 | 48 | 48 | 22 | 34 | 48 | 21 | 47 | 14 | 22 | 31 | 15 | 23 | 10 | 16 | 22 |
34 | 48 | 48 | 23 | 35 | 48 | 22 | 48 | 15 | 23 | 32 | 15 | 24 | 10 | 16 | 23 |
35 | 48 | 48 | 23 | 36 | 48 | 23 | 48 | 15 | 23 | 33 | 16 | 25 | 11 | 16 | 23 |
36 | 48 | 48 | 24 | 37 | 48 | 23 | 48 | 15 | 24 | 34 | 16 | 25 | 11 | 17 | 24 |
37 | 48 | 48 | 25 | 38 | 48 | 24 | 48 | 16 | 25 | 35 | 17 | 26 | 11 | 17 | 25 |
38 | 48 | 48 | 25 | 39 | 48 | 25 | 48 | 16 | 25 | 36 | 17 | 27 | 12 | 18 | 25 |
39 | 48 | 48 | 26 | 40 | 48 | 25 | 48 | 17 | 26 | 37 | 18 | 27 | 12 | 18 | 26 |
40 | 48 | 48 | 27 | 41 | 48 | 26 | 48 | 17 | 27 | 38 | 18 | 28 | 12 | 19 | 27 |
41 | 48 | 48 | 27 | 42 | 48 | 26 | 48 | 18 | 27 | 39 | 19 | 29 | 12 | 19 | 27 |
42 | 48 | 48 | 28 | 43 | 48 | 27 | 48 | 18 | 28 | 40 | 19 | 30 | 13 | 20 | 28 |
43 | 48 | 48 | 29 | 44 | 48 | 28 | 48 | 18 | 29 | 41 | 20 | 30 | 13 | 20 | 29 |
44 | 48 | 48 | 29 | 45 | 48 | 28 | 48 | 19 | 29 | 42 | 20 | 31 | 13 | 21 | 29 |
45 | 48 | 48 | 30 | 47 | 48 | 29 | 48 | 19 | 30 | 43 | 20 | 32 | 14 | 21 | 30 |
46 | 48 | 48 | 31 | 48 | 48 | 30 | 48 | 20 | 31 | 44 | 21 | 32 | 14 | 22 | 31 |
47 | 48 | 48 | 31 | 48 | 48 | 30 | 48 | 20 | 31 | 44 | 21 | 33 | 14 | 22 | 31 |
48 | 48 | 48 | 32 | 48 | 48 | 31 | 48 | 21 | 32 | 45 | 22 | 34 | 15 | 23 | 32 |
For SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.895 kPa.
- This table is for use with tables in Section R404.1.3.2 that specify the minimum bar size and maximum spacing of vertical wall reinforcement for foundation walls and above-grade walls. Reinforcement specified in tables in Section R404.1.3.2 is based on Grade 60 steel reinforcement.
- Bar spacing shall not exceed 48 inches on center and shall be not less than one-half the nominal wall thickness.
- For Grade 50 steel bars (ASTM A 996, Type R), use spacing for Grade 40 bars or interpolate between Grades 40 and 60.
Related Code Sections
R404.1.2 Foundations, Design of Masonry Foundation Walls
Masonry foundation walls shall be designed and constructed in accordance with the provisions of this section or in accordance with the provisions ...
Residential Code 2015 of New York State > 4 Foundations > R404 Foundation and Retaining Walls > R404.1 Concrete and Masonry Foundation Walls > R404.1.2 Design of Masonry Foundation Walls
R404.1.2.1 Foundations, Masonry Foundation Walls
Concrete masonry and clay masonry foundation walls shall be constructed as set forth in Table R404.1.1(1), R404.1.1(2), R404.1.1(3) or R404.1.1(4 ...
2020 Residential Code of New York State > 4 Foundations > R404 Foundation and Retaining Walls > R404.1 Concrete and Masonry Foundation Walls > R404.1.2 Design of Masonry Foundation Walls > R404.1.2.1 Masonry Foundation Walls
2109.5.3.1 Masonry, Minimum Thickness
are nonexpansive; and Masonry is laid in running bond using Type M or S mortar.
TABLE 2109.5.3.1
FOUNDATION WALL CONSTRUCTION
WALL CONSTRUCTION ...
2010 Building Code of NY > 21 Masonry > 2109 Empirical Design of Masonry > 2109.5 Thickness of Masonry > 2109.5.3 Foundation Walls > 2109.5.3.1 Minimum Thickness
1807.1.6 Soils and Foundations, Prescriptive Design of Concrete and Masonry Foundation Walls
Concrete and masonry foundation walls that are laterally supported at the top and bottom shall be permitted to be designed and constructed ...
Building Code 2015 of New York State > 18 Soils and Foundations > 1807 Foundation Walls, Retaining Walls and Embedded Posts and Poles > 1807.1 Foundation Walls > 1807.1.6 Prescriptive Design of Concrete and Masonry Foundation Walls
1807.1.6 Soils and Foundations, Prescriptive Design of Concrete and Masonry Foundation Walls
Concrete and masonry foundation walls that are laterally supported at the top and bottom shall be permitted to be designed and constructed ...
2020 Building Code of New York State > 18 Soils and Foundations > 1807 Foundation Walls, Retaining Walls and Embedded Posts and Poles > 1807.1 Foundation Walls > 1807.1.6 Prescriptive Design of Concrete and Masonry Foundation Walls