2409.4 Design Formula
JUMP TO FULL CODE CHAPTER
Where:
The design of the glazing shall be based on
where Fg is the maximum load on the glass determined from the load combinations above, and Fga is the maximum allowable load on the glass, computed by the following formula:
Where:
Glass in floors and sidewalks shall be designed to resist the most critical of the following combinations of loads:
Fg = 2Fu + D
(Equation 24-11)
Fg = (8Fc /A) + D
(Equation 24-12)
Fg = Fa + D
(Equation 24-13)
Where:
A | = | Area of rectangular glass, ft2 (m2). |
D | = | Glass dead load (psf) = 13 tg (for SI: 0.0245 tg, kN/m2). |
tg | = | Total glass thickness, inches (mm). |
Fa | = | Actual intended use load, psf (kN/m2). |
Fc | = | Concentrated load, pounds (kN). |
Fg | = | Total load, psf (kN/m2) on glass. |
Fu | = | Uniformly distributed load, psf (kN/m2). |
The design of the glazing shall be based on
Fg ≤ Fga
(Equation 24-14)
where Fg is the maximum load on the glass determined from the load combinations above, and Fga is the maximum allowable load on the glass, computed by the following formula:
Fga = 0.67 c2 Fge
(Equation 24-15)
Where:
Fge | = | Maximum allowable equivalent load, psf (kN/m2), determined from Figures 2404(1) through 2404(12) for the applicable glass dimensions and thickness; and |
c2 | = | Factor determined from Table 2404.2 based on glass type. |
The factor, c2, for laminated glass found in Table 2404.2 shall apply to two-ply laminates only. The value of Fa shall be doubled for dynamic applications.
Related Code Sections
2409.4 Glass and Glazing, Design Formula
Glass in floors and sidewalks shall be designed to resist the most critical of the following combinations of loads:
F g = 2 F u + D ...
NYC Building Code 2008 > 24 Glass and Glazing > 2409 Glass in Floors and Sidewalks > 2409.4 Design Formula
1801.2 Soils and Foundations, Design
Allowable bearing pressures, allowable stresses and design formulas provided in this chapter shall be used with the allowable stress design load ...
1801.2 Soils and Foundations, Design
Allowable bearing pressures, allowable stresses and design formulas provided in this chapter shall be used with the allowable stress design load ...
Article 19 Reinforced Concrete and Plain Concrete Construction [PDF] (page 41)
) at any point; in addition to this, the reinforced concrete portion shall be designed to carry, in accordance with formula (11), all floor loads brought ...
1809.2.3.2.1 Soils and Foundations, Design in Seismic Design Category C
Where a structure is assigned to Seismic Design Category C in accordance with Section 1616, the minimum volumetric ratio of spiral reinforcement ...
NYC Building Code 2008 > 18 Soils and Foundations > 1809 Driven Pile Foundations > 1809.2 Precast Concrete Piles > 1809.2.3 Precast Prestressed Piles > 1809.2.3.2 Design > 1809.2.3.2.1 Design in Seismic Design Category C