3305.3.2.1 Design Drawings
JUMP TO FULL CODE CHAPTER
Site-specific formwork design drawings prepared by a registered design professional shall be required in the following cases:
- For concrete formwork in a structure classified as a major building; or
- Wherever the shore or form height exceeds 14 feet (4267 mm); or
- Wherever the total vertical load on the forms exceeds 150 pounds per square foot (732 kg/m2); or
- Wherever power buggies are used; or
- Wherever multi-stage shores are used; or
- Wherever the slab thicknesses or beam heights equal or exceed 10 inches; or
- Wherever there are concentrated loads exceeding 2000 pounds (907 kg) imposed on the formwork; or
- Wherever there are loads imposed on existing structures in accordance with Section 3305.3.1.2.1.
Related Code Sections
3305.3.2.1 Safeguards During Construction or Demolition, Design Drawings
Site-specific formwork design drawings prepared by a registered design professional shall be required in the following cases: For concrete formwork ...
NYC Building Code 2014 > 33 Safeguards During Construction or Demolition > 3305 Material Placement and Installation > 3305.3 Concrete Formwork > 3305.3.2 Design of Concrete Formwork > 3305.3.2.1 Design Drawings
2210.3.2 Steel, Truss Design Drawings
The truss design drawings shall conform to the requirements of Section B2.3 of AISI S214 and shall be provided with the shipment of trusses delivered ...
NYC Building Code 2014 > 22 Steel > 2210 Cold-Formed Steel Light-Frame Construction > 2210.3 Trusses > 2210.3.2 Truss Design Drawings
2303.4.1 Wood, Truss Design Drawings
Truss construction documents shall be prepared by a registered design professional and shall be provided to the commissioner and approved prior ...
NYC Building Code 2008 > 23 Wood > 2303 Minimum Standards and Quality > 2303.4 Trusses > 2303.4.1 Truss Design Drawings
2303.4.1.1 Wood, Truss Design Drawings
individual truss shall be provided to the commissioner and approved prior to installation. Truss design drawings shall also be provided with the shipment ...
NYC Building Code 2014 > 23 Wood > 2303 Minimum Standards and Quality > 2303.4 Trusses > 2303.4.1 Design > 2303.4.1.1 Truss Design Drawings
3314.10.1 Safeguards During Construction or Demolition, Suspended Elements to Be Kept Vertical and Parallel
provided such occurs in accordance with design drawings prepared by a registered design professional. Such design drawings shall be based ...
NYC Building Code 2014 > 33 Safeguards During Construction or Demolition > 3314 Scaffolds > 3314.10 Suspended Scaffold > 3314.10.1 Suspended Elements to Be Kept Vertical and Parallel