1808.9.3.1 Design Details for Piles and Grade Beams
JUMP TO FULL CODE CHAPTER
Piles shall be designed and constructed to withstand maximum imposed curvatures from earthquake ground motions and structure response. Curvatures shall include free-field soil strains modified for soil-pile-structure interaction coupled with pile deformations induced by lateral pile resistance to structure seismic forces. Concrete piles on Site Class E or F sites, as determined in Section 1613.5.2, shall be designed and detailed in accordance with Sections 21.12.4.1, 21.12.4.2 and 21.12.4.3 of ACI 318 within seven pile diameters of the pile cap and the interfaces of soft to medium stiff clay or liquefiable strata. For precast prestressed concrete piles, detailing provisions as given in Sections 1809.6.3.2.1 and 1809.6.3.2.2 shall apply. Grade beams shall be designed as beams in accordance with ACI 318, Chapter 21. When grade beams have the capacity to resist the forces from the load combinations in Section 1605.4, they need not conform to ACI 318, Chapter 21.
Related Code Sections
1808.9.3.1 Soils and Foundations, Design Details for Piles and Grade Beams
to structure seismic forces. Concrete piles on Site Class E or F sites, as determined in Section 1613.5.2, shall be designed and detailed in accordance ...
NYC Building Code 2014 > 18 Soils and Foundations > 1808 Deep Foundations > 1808.9 Seismic Design Categories C & D > 1808.9.3 Seismic Design Category D > 1808.9.3.1 Design Details for Piles and Grade Beams
1808.2.23.2.1 Soils and Foundations, Design Details for Piers, Piles and Grade Beams
be designed and detailed in accordance with Sections 21.4.4.1, 21.4.4.2 and 21.4.4.3 of ACI 318 within seven pile diameters of the pile cap ...
NYC Building Code 2008 > 18 Soils and Foundations > 1808 Pier and Pile Foundations > 1808.2 Piers and Piles—General Requirements > 1808.2.23 Seismic Design of Piers or Piles > 1808.2.23.2 Seismic Design Category D > 1808.2.23.2.1 Design Details for Piers, Piles and Grade Beams
§27-694 Foundations, Capping and Bracing of Piles
, and only where the piles project above the future grade and will be readily accessible for visual inspection at all times, the tops of the piles may ...
NYC 1968 Code (Vol I) > 11 Foundations > 7 Pile Foundations-General Requirements > §27-694 Capping and Bracing of Piles
1808.2.23.2.3 Soils and Foundations, Flexural Strength
strength. The connection between batter piles and grade beams or pile caps shall be designed to resist the nominal strength of the pile ...
NYC Building Code 2008 > 18 Soils and Foundations > 1808 Pier and Pile Foundations > 1808.2 Piers and Piles—General Requirements > 1808.2.23 Seismic Design of Piers or Piles > 1808.2.23.2 Seismic Design Category D > 1808.2.23.2.3 Flexural Strength
1808.2.23.1.2 Soils and Foundations, Design Details
Pier or pile moments, shears and lateral deflections used for design shall be established considering the nonlinear interaction of the shaft and soil ...
NYC Building Code 2008 > 18 Soils and Foundations > 1808 Pier and Pile Foundations > 1808.2 Piers and Piles—General Requirements > 1808.2.23 Seismic Design of Piers or Piles > 1808.2.23.1 Seismic Design Category C > 1808.2.23.1.2 Design Details