1910.106(d)(3) Design, Construction, and Capacity of Storage Cabinets
JUMP TO FULL CODE CHAPTER
Not more than 60 gallons of Category 1, 2, or 3 flammable liquids, nor more than 120 gallons of Category 4 flammable liquids may be stored in a storage cabinet.
Storage cabinets shall be designed and constructed to limit the internal temperature to not more than 325 deg. F. when subjected to a 10-minute fire test using the standard time-temperature curve as set forth in Standard Methods of Fire Tests of Building Construction and Materials, NFPA 251-1969, which is incorporated by reference as specified in Sec. 1910.6. All joints and seams shall remain tight and the door shall remain securely closed during the fire test. Cabinets shall be labeled in conspicuous lettering, "Flammable - Keep Fire Away."
Metal cabinets constructed in the following manner shall be deemed to be in compliance. The bottom, top, door, and sides of cabinet shall be at least No. 18 gage sheet iron and double walled with 1 1/2- inch air space. Joints shall be riveted, welded or made tight by some equally effective means. The door shall be provided with a three-point lock, and the door sill shall be raised at least 2 inches above the bottom of the cabinet.
Wooden cabinets constructed in the following manner shall be deemed in compliance. The bottom, sides, and top shall be constructed of an approved grade of plywood at least 1 inch in thickness, which shall not break down or delaminate under fire conditions. All joints shall be rabbetted and shall be fastened in two directions with flathead woodscrews. When more than one door is used, there shall be a rabbetted overlap of not less than 1 inch. Hinges shall be mounted in such a manner as not to lose their holding capacity due to loosening or burning out of the screws when subjected to the fire test.
Related Code Sections
1910.106(d)(3) Hazardous Materials, Design, Construction, and Capacity of Storage Cabinets
in a storage cabinet. Storage cabinets shall be designed ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(d) Container and Portable Tank Storage > 1910.106(d)(3) Design, Construction, and Capacity of Storage Cabinets
1910.106(d)(2) Hazardous Materials, Design, Construction, and Capacity of Containers
Flammable liquid containers shall be in accordance with Table H-12, except that glass or plastic containers of no more than 1-gallon capacity may be used ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(d) Container and Portable Tank Storage > 1910.106(d)(2) Design, Construction, and Capacity of Containers
1910.103(c)(1)(vi) Hazardous Materials, Equipment Assembly
be supervised by personnel familiar with proper practices and with reference to their construction and use ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.103 Hydrogen > 1910.103(c) Liquefied Hydrogen Systems > 1910.103(c)(1) Design > 1910.103(c)(1)(vi) Equipment Assembly
1910.106(d)(4)(v) Hazardous Materials, Storage in Inside Storage Rooms
In every inside storage room there shall be maintained one clear aisle at least 3 feet wide. Containers over 30 gallons capacity shall not be stacked ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(d) Container and Portable Tank Storage > 1910.106(d)(4) Design and Construction of Inside Storage Rooms > 1910.106(d)(4)(v) Storage in Inside Storage Rooms
1910.106(d) Hazardous Materials, Container and Portable Tank Storage
in a storage cabinet. Storage cabinets shall be designed ...