22.2.4 Design Assumptions for Prestressing Reinforcement
Go To Full Code Chapter
22.2.4.1
For members with bonded prestressing reinforcement conforming to 20.3.1, stress at nominal flexural strength, fps, shall be calculated in accordance with 20.3.2.3.
22.2.4.2
For members with unbonded prestressing reinforcement conforming to 20.3.1, fps shall be calculated in accordance with 20.3.2.4.