3403.6.2 Design and Fabrication of System Components
Go To Full Code Chapter
Piping system components shall be designed and fabricated in accordance with Chapter 5 of NFPA 30, except as modified by this section.
3403.6.2.1 Special Materials
Low-melting-point materials (such as aluminum, copper or brass), materials that soften on fire exposure (such as nonmetallic materials) and nonductile material (such as cast iron) shall be acceptable for use underground in accordance with ASME B31.9. When such materials are used outdoors in above-ground piping systems or within buildings, they shall be in accordance with ASME B31.9 and one of the following:
- Suitably protected against fire exposure.
- Located where leakage from failure would not unduly expose people or structures.
- Located where leakage can be readily controlled by operation of accessible remotely located valves.
In all cases, nonmetallic piping shall be used in accordance with Section 5.3.6 of NFPA 30.
Upcodes Diagrams
Related Code Sections
3403.6.2 Flammable and Combustible Liquids, Design and Fabrication of System Components
Piping system components shall be designed and fabricated in accordance with Chapter 5 of NFPA 30, except as modified by this section ...
5703.6.2 Flammable and Combustible Liquids, Design and Fabrication of Piping Systems and Components
Piping system components shall be designed and fabricated in accordance with the applicable standard listed in Table 5703.6.2 and Chapter 27 of NFPA ...
5703.6.2 Flammable and Combustible Liquids, Design and Fabrication of Piping Systems and Components
Piping system components shall be designed and fabricated in accordance with the applicable standard listed in Table 5703.6.2 and Chapter 27 of NFPA ...
608.4.1 Building Services and Systems, Design Standards
The design, fabrication and assembly of system components shall be suitable for the working pressures, temperatures and structural stresses ...
610.4.1 Building Services and Systems, Design Standards
The design, fabrication and assembly of system components shall be suitable for the working pressures, temperatures and structural stresses ...