Piping system components shall be designed and fabricated in accordance with the applicable standard listed in Table 5703.6.2 and Chapter 27 of NFPA 30, except as modified by Section 5703.6.2.1.
TABLE 5703.6.2
PIPING STANDARDS
PIPING USE STANDARD
Power piping ASME B31.1
Process piping ASME B31.3
Pipeline transportation systems for liquid hydrocarbons and other liquids ASME B31.4
Building services piping ASME B31.9
Double containment piping UL 971A, UL 1369
5703.6.2.1 Special Materials
Low-melting-point materials (such as aluminum, copper or brass), materials that soften on fire exposure (such as nonmetallic materials) and nonductile material (such as cast iron) shall be acceptable for use underground in accordance with the applicable standard listed in Table 5703.6.2. Where such materials are used outdoors in above-ground piping systems or within buildings, they shall be in accordance with the applicable standard listed in Table 5703.6.2 and one of the following:
  1. Suitably protected against fire exposure.
  2. Located where leakage from failure would not unduly expose people or structures.
  3. Located where leakage can be readily controlled by operation of remotely located valves in a location provided with ready access.
In all cases, nonmetallic piping shall be used in accordance with Section 27.4.6 of NFPA 30.
Upcodes Diagrams

Related Code Sections

G2412.1 Fuel Gas, (401.1) Scope
This section shall govern the design, installation, modification and maintenance of piping systems. The applicability of this code to piping systems ...
G2412.1 Fuel Gas, (401.1) Scope
This section shall govern the design, installation, modification and maintenance of piping systems. The applicability of this code to piping systems ...
401.1 Gas Piping Installations, Scope
This chapter shall govern the design, installation, modification and maintenance of piping systems. The applicability of this code to piping systems ...