902.10 Depth to Rock Strata or 50 Percent by Volume Rock Fragments
Go To Full Code Chapter
Not less than 60 inches (1524 mm) of soil shall be present over uncreviced, impermeable bedrock. Where the soil contains 50-percent coarse fragments by volume in the upper 24 inches (610 mm), a mound shall not be installed except where there is not less than 24 inches (610 mm) of permeable, unsaturated soil with less than 50-percent coarse fragments located beneath this layer.