11B-228 Depositories, Vending Machines, Change Machines, Mail Boxes, Fuel Dispensers,and Electric Vehicle Charging Stations
Where provided, at least one of each type of depository, vending machine, change machine, and fuel dispenser shall comply with Section 11B-309. Electric vehicle charging stations shall comply with Section 11B-228.3.
Exception: Drive-up only depositories shall not be required to comply with Section 11B-309.
Where electric vehicle charging stations (EVCS) are provided, EVCS shall be provided in accordance with Section 11B-228.3.
Where new EVCS are added to a facility with existing EVCS, the requirements of Section 11B-812 shall apply only to the new EVCS installed. Alterations to existing EVCS shall comply with Section 11B-228.3.
Where EV chargers are provided, operable parts on all EV chargers shall comply with Section 11B-309.4.
EVCS complying with Section 11B-812 shall be provided in accordance with Section 11B-228.3.2. Where EVCS are provided in more than one facility on a site, the number of EVCS complying with Section 11B-228.3.2 provided on the site shall be calculated according to the number required for each facility. Where an EV charger can simultaneously charge more than one vehicle, the number of EV chargers provided shall be considered equivalent to the number of electric vehicles that can be simultaneously charged.
Exceptions:
- EVCS not available to the general public and intended for use by a designated vehicle or driver shall not be required to comply with Section 11B-228.3.2. Examples include, but are not limited to, EVCS serving public or private fleet vehicles and EVCS assigned to an employee.
- In public housing facilities, EVCS intended for use by an EV owner or operator at their residence shall not be required to comply with Section 11B-228.3.2.
Where EVCS are provided for public use or common use, EVCS complying with Section 11B-812 shall be provided in accordance with Table 11B-228.3.2.1. Where new EVCS are installed in facilities with existing EVCS, the "Total Number of EVCS at a Facility" in Table 11B-228.3.2.1 shall include both existing and new EVCS.
Exception: All drive-up EVCS shall comply with Section 11B-812.
ELECTRIC VEHICLE CHARGING STATIONS FOR PUBLIC USE AND COMMON USE
TOTAL NUMBER OF EVCS AT A FACILITY1 | MINIMUM NUMBER (by type) OF EVCS REQUIRED TO COMPLY WITH SECTION 11B-8121 | ||
Van Accessible | Standard Accessible | Ambulatory | |
1 to 4 | 1 | 0 | 0 |
5 to 25 | 1 | 1 | 0 |
26 to 50 | 1 | 1 | 1 |
51 to 75 | 1 | 2 | 2 |
76 to 100 | 1 | 3 | 3 |
101 and over | 1, plus 1 for each 300, or fraction thereof, over 100 | 3, plus 1 for each 60, or fraction thereof, over 100 | 3, plus 1 for each 50, or fraction thereof, over 100 |
- Where an EV charger can simultaneously charge more than one vehicle, the number of EVCS provided shall be considered equivalent to the number of electric vehicles that can be simultaneously charged.