// CODE SNIPPET
B.5.4 Demand (GPM) Corresponding to Fixture Load (WSFU)
Go To Full Code Chapter
To determine the maximum probable demand in gallons per minute corresponding to any given load in water supply fixture units, reference should be made to Table B.5.4, in which the values have been arranged for convenient conversion of maximum probable demand from terms of water supply fixture units of load to gallons per minute of flow. Refer to the increased number of WSFU to GPM listings in Appendix M to avoid the need to interpolate between the values in Table B.5.4.
Note in the table that the maximum probable demand corresponding to a given number of water supply fixture units is generally much higher for a system in which water closets are flushed by means of direct-supply flushometer valves than for a system in which the water closets are flushed by other types of flushing devices.
The difference in maximum probable demand between the two systems diminishes as the total number of fixture units of load rises. At 1,000 water supply fixture units, the maximum probable demand in both types of systems is the same, 210 gpm.
Where a part of the system does not supply flushometer water closets, such as in the case with hot water supply piping and some cold water supply branches, the maximum probable demand corresponding to a given number of water supply fixture units may be determined from the values given for a system in which water closets are flushed by flush tanks.
Table B.5.4 TABLE FOR CONVERTING DEMAND IN WSFU TO GPM1, 4 | |||||
WSFU | GPM Flush Tanks2 | GPM Flush Valves3 | WSFU | GPM Flush Tanks2 | GPM Flush Valves3 |
3 | 3 | 120 | 49 | 74 | |
4 | 4 | 140 | 53 | 78 | |
5 | 4.5 | 22 | 160 | 57 | 83 |
6 | 5 | 23 | 180 | 61 | 87 |
7 | 6 | 24 | 200 | 65 | 91 |
8 | 7 | 25 | 225 | 70 | 95 |
9 | 7.5 | 26 | 250 | 75 | 100 |
10 | 8 | 27 | 300 | 85 | 110 |
11 | 8.5 | 28 | 400 | 105 | 125 |
12 | 9 | 29 | 500 | 125 | 140 |
13 | 10 | 29.5 | 750 | 170 | 175 |
14 | 10.5 | 30 | 1000 | 210 | 210 |
15 | 11 | 31 | 1250 | 240 | 240 |
16 | 12 | 32 | 1500 | 270 | 270 |
17 | 12.5 | 33 | 1750 | 300 | 300 |
18 | 13 | 33.5 | 2000 | 325 | 325 |
19 | 13.5 | 34 | 2500 | 380 | 380 |
20 | 14 | 35 | 3000 | 435 | 435 |
25 | 17 | 38 | 4000 | 525 | 525 |
30 | 20 | 41 | 5000 | 600 | 600 |
40 | 25 | 47 | 6000 | 650 | 650 |
50 | 29 | 51 | 7000 | 700 | 700 |
60 | 33 | 55 | 8000 | 730 | 730 |
80 | 39 | 62 | 9000 | 760 | 760 |
100 | 44 | 68 | 10,000 | 790 | 790 |
NOTES:
- This table converts water supply demands in water supply fixture units (WSFU) to required water flow in gallons per minute (GPM) for the purpose of pipe sizing.
- This column applies to the following portions of piping systems:
- Hot water piping;
- Cold water piping that serves no water closets; and
- Cold water piping that serves water closets other than the flush valve type.
- This column applies to portions of piping systems where the water closets are the flush valve type.
- Refer to Appendix M for WSFU to GPM listings between those in Table B.5.4 to avoid the need to interpolate between the values in Table B.5.4.
Related Code Sections
B.5.4 Sizing the Building Water Supply and Distribution Piping Systems, Demand (GPM) Corresponding to Fixture Load (WSFU)
To determine the maximum probable demand in gallons per minute corresponding to any given load in water supply fixture units, reference should ...
10.14.3 Water Supply and Distribution Systems, Sizing Water Distribution Piping
of water supply fixture units (WSFU) as shown in Table 10.14.2A and the relationship between the load in WSFU and the supply demand in gallons per ...
B.7 Sizing the Building Water Supply and Distribution Piping Systems, Simplified Method for Sizing Systems in Relatively Low Buildings
, adjacent to all fixture unit notations, the demand in gallons per minute corresponding to the various fixture unit loads in accordance with Table B.5.3 ...