1010.1.9.8 Delayed Egress
JUMP TO FULL CODE CHAPTER
Delayed egress locking systems shall be permitted to be installed on doors serving the following occupancies in buildings that are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or an approved automatic smoke or heat detection system installed in accordance with Section 907.
- Group B, F, I, M, R, S and U occupancies.
- Group E classrooms with an occupant load of less than 50.
Exception: Delayed egress locking systems shall be permitted to be installed on exit or exit access doors, other than the main exit or exit access door, serving a courtroom in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
The delayed egress locking system shall be installed and operated in accordance with all of the following:
- The delay electronics of the delayed egress locking system shall deactivate upon actuation of the automatic sprinkler system or automatic fire detection system, allowing immediate free egress.
- The delay electronics of the delayed egress locking system shall deactivate upon loss of power controlling the lock or lock mechanism, allowing immediate free egress.
- The delayed egress locking system shall have the capability of being deactivated at the fire command center and other approved locations.
- An attempt to egress shall initiate an irreversible process that shall allow such egress in not more than 15 seconds when a physical effort to exit is applied to the egress side door hardware for not more than 3 seconds. Initiation of the irreversible process shall activate an audible signal in the vicinity of the door. Once the delay electronics have been deactivated, rearming the delay electronics shall be by manual means only.Exception: Where approved, a delay of not more than 30 seconds is permitted on a delayed egress door.
- The egress path from any point shall not pass through more than one delayed egress locking system.Exceptions:
- In Group I-2 or I-3 occupancies, the egress path from any point in the building shall pass through not more than two delayed egress locking systems provided that the combined delay does not exceed 30 seconds.
- In Group I-1 or I-4 occupancies, the egress path from any point in the building shall pass through not more than two delayed egress locking systems provided the combined delay does not exceed 30 seconds and the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
- A sign shall be provided on the door and shall be located above and within 12 inches (305 mm) of the door exit hardware:
- 6.1. For doors that swing in the direction of egress, the sign shall read: PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS.
- 6.2. For doors that swing in the opposite direction of egress, the sign shall read: PULL UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS.
- 6.3. The sign shall comply with the visual character requirements in ICC A117.1.
- Emergency lighting shall be provided on the egress side of the door.
- The delayed egress locking system units shall be listed in accordance with UL 294.
Related Code Sections
1010.1.9.8 Means of Egress, Delayed Egress
Delayed egress locking systems shall be permitted to be installed on doors serving the following occupancies in buildings that are equipped ...
Building Code 2018 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.9 Door Operations > 1010.1.9.8 Delayed Egress
1010.2.13 Means of Egress, Delayed Egress
Delayed egress locking systems shall be permitted to be installed on doors serving the following occupancies in buildings that are equipped ...
Building Code 2021 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.2 Door Operations > 1010.2.13 Delayed Egress
Section 1010 Means of Egress, Doors, Gates and Turnstiles
hospital. Delayed egress locking systems shall ...
Section 1010 Means of Egress, Doors, Gates and Turnstiles
in accordance with UL 294. Delayed egress locking systems ...
407.3.5 Accessible Routes, Door Delay
Elevator doors shall remain fully open in response to a car call for 3 seconds minimum ...
2018 Illinois Accessibility Code > 4 Accessible Routes > 407 Elevators > 407.3 Elevator Door Requirements > 407.3.5 Door Delay