5.4.4.1.3 Deflection of Car Enclosure Walls
Go To Full Code Chapter
The car enclosure walls shall be of such strength and designed and supported so that when subjected to a force of 334 N (75 lbf) applied horizontally at any point on the walls of the enclosure, the deflection will not reduce the running clearance below 19 mm (0.75 in.) nor to more than 25 mm (1 in.).
Upcodes Diagrams
Related Code Sections
5.4.4.1.3 Special Application Elevators, Deflection of Car Enclosure Walls
The car enclosure walls shall be of such strength and designed and supported so that when subjected to a force of 334 N (75 lbf) applied horizontally ...
7.5.1.1.3 Dumbwaiters and Material Lifts,
or falling rated load on the car, the car enclosure walls will not deflect or deform to the extent that the running clearances are reduced below ...
7.2.1.1.2 Dumbwaiters and Material Lifts,
be of such strength and designed and supported so that when subjected to a leaning or falling rated load on the car, the car enclosure walls will not deflect ...
5.4.4 Special Application Elevators, Car Enclosures, Car Doors, and Gates
The car enclosure walls shall be of such strength and designed ...
2.14.1.3 Electric Elevators, Strength and Deflection of Enclosure Walls
The enclosure walls shall be designed and installed to withstand a force of 330 N (75 lbf) applied horizontally at any point on the walls ...