1309.3.10.4 Defective Brazed Joints
JUMP TO FULL CODE CHAPTER
Brazed
joints that are identified as defective under the
conditions of Section 1309.3.10.3(2) or Section
1309.3.10.3(5) shall be replaced. [NFPA
99:5.1.10.4.7.5,5.3.6.10.5]
Brazed joints that are identified as defective under the conditions of Section 1309.3.10.3(1), Section 1309.3.10.3(3), Section 1309.3.10.3(4), Section 1309.3.10.3(6), or Section 1309.3.10.3(7) shall be permitted to be repaired, except that no joint shall be reheated more than once before being replaced. [NFPA 99:5.1.10.4.7.6, 5.3.6.10.6]
Brazed joints that are identified as defective under the conditions of Section 1309.3.10.3(1), Section 1309.3.10.3(3), Section 1309.3.10.3(4), Section 1309.3.10.3(6), or Section 1309.3.10.3(7) shall be permitted to be repaired, except that no joint shall be reheated more than once before being replaced. [NFPA 99:5.1.10.4.7.6, 5.3.6.10.6]
Related Code Sections
1309.10.4 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Defective Brazed Joints
Brazed joints that are identified as defective under the conditions of Section
1309.10.3(2) or Section 1309.10.3(5) shall be replaced.
Brazed ...
California Plumbing Code 2019 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1309.0 Joints and Connections > 1309.10 Inspection of Brazed Joints > 1309.10.4 Defective Brazed Joints
1309.3.10.4 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Defective Brazed Joints
Brazed
joints that are identified as defective under the
conditions of Section 1309.3.10.3(2) or Section
1309.3.10.3(5) shall be replaced. [NFPA
99 ...
California Plumbing Code 2016 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1309.0 Joints and Connections > 1309.3 Brazed Joints and Fittings > 1309.3.10 Inspection of Brazed Joints > 1309.3.10.4 Defective Brazed Joints
605.1.1 Water Supply and Distribution, Brazed Joints
Brazed joints between copper or copper alloy pipe or tubing and fittings shall be made with brazing alloys having a liquid temperature above 1000°F ...
California Plumbing Code 2016 > 6 Water Supply and Distribution > 605.0 Joints and Connections > 605.1 Copper or Copper Alloy Pipe, Tubing, and Joints > 605.1.1 Brazed Joints
605.1.1 Water Supply and Distribution, Brazed Joints
Brazed joints between copper
or copper alloy pipe or tubing and fittings shall be made
with brazing alloys having a liquid temperature above
1000°F ...
California Plumbing Code 2019 > 6 Water Supply and Distribution > 605.0 Joints and Connections > 605.1 Copper or Copper Alloy Pipe, Tubing, and Joints > 605.1.1 Brazed Joints
705.3.1 Sanitary Drainage, Brazed Joints
Brazed joints between copper or copper alloy pipe and fittings shall be made with brazing alloys having a liquid temperature above
1000°F (538°C ...
California Plumbing Code 2016 > 7 Sanitary Drainage > 705.0 Joints and Connections > 705.3 Copper or Copper Alloy Pipe (DWV) and Joints > 705.3.1 Brazed Joints