609.6.2 Deep Fat Fryers
JUMP TO FULL CODE CHAPTER
When a deep fat fryer is installed in a cooking area, Class K portable fire extinguishers shall be provided as follows:
- For up to four fryers individually having a maximum cooking medium capacity of 80 pounds (36.3 kg) and a maximum surface area of 6 square feet (0.55 m2): One having a minimum 11/2 gallon (6 L) capacity.
- For every additional group of up to four fryers, individually having a maximum cooking medium capacity of 80 pounds (36.3 kg) and a maximum surface area of 6 square feet (0.55 m2) each: One additional Class K portable fire extinguisher having a minimum 1 1/2gallon (6 L) capacity.
- For individual fryers having a maximum cooking medium capacity exceeding 80 pounds (36.3 kg) or 6 square feet (0.55 m2) in surface area: Provide Class K portable fire extinguishers in accordance with the portable fire extinguisher manufacturer's recommendations.
Related Code Sections
Reference Standard 15 Chimneys and Gas Vents [PDF] (page 2)
Service Equipment -Baking and Roasting Ovens................................…...1986 ANSI-Z83.13 Gas Food Service Equipment -Deep Fat Fryers ...
Reference Standard 15 Chimneys and Gas Vents [PDF] (page 1)
Appliances.........................……………………………... 1987 ANSI- Z21.27 Hotel and Restaurant Gas Deep Fat Fryers, and Addenda Z21.27a-1975, Z21.27b-1978.. 1974 ...
Reference Standard 15 Chimneys and Gas Vents [PDF] (page 4)
Ovens. ANSI-Z83.13-1986—Gas Food Service Equipment - Deep Fat Fryers. ANSI-Z83.14-1986—Gas Food Service Equipment - Counter Appliances. ANSI-Z83.15-1986 ...
Reference Standard 14 Heating and Combustion Equipment [PDF] (page 8)
- Baking and Roasting Ovens. ANSI-Z83.13-1986 - Gas Food Service Equipment - Deep Fat Fryers. ANSI-Z83.14-1986 - Gas Food Service Equipment - Counter ...
Reference Standard 14 Heating and Combustion Equipment [PDF] (page 1)
Appliances........………..............……………………….. 1987 Hotel and Restaurant Gas Deep Fat Fryers, and Addenda Z21.27a-1975, Z21.27b-1978... 1974 Commercial Gas ...